beautypg.com

York ZJ R-410A User Manual

Page 77

background image

251934-YTG-G-0708

Johnson Controls Unitary Products

77

300

(25)

208-3-60 23.0

160

31.5

3.7

38.6

10.0

None

-

-

-

165.1

200

E18

13.5

1

37.5

165.1

200

E36

27.0

2

74.9

165.1

200

E54

40.6

2

112.7

201.6

225

E72

54.1

2

150.2

210.9

225

230-3-60 23.0

160

31.5

3.7

38.6

10.0

None

-

-

-

165.1

200

E18

18.0

1

43.3

165.1

200

E36

36.0

2

86.6

169.0

200

E54

54.0

2

129.9

190.7

225

E72

72.0

2

173.2

234.0

250

460-3-60 12.2

87

17.1

1.9

19.3

5.0

None

-

-

-

85.5

100

E18

18.0

1

21.7

85.5

100

E36

36.0

2

43.3

85.5

100

E54

54.0

2

65.0

95.3

110

E72

72.0

2

86.6

117.0

125

575-3-60 8.7

62

13.5

1.5

15.4

4.0

None

-

-

-

64.1

70

E18

18.0

1

17.3

64.1

70

E36

36.0

2

34.6

67.6

70

E54

54.0

2

52.0

76.2

90

E72

72.0

2

69.3

93.5

100

1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.

ZJ180-300 - High Static Drive With Powered Convenience Outlet (Continued)

Size

(Tons)

Volt

Compressors

(each)

OD Fan

Motors

(each)

Supply
Blower

Motor

Pwr

Conv

Outlet

Electric Heat Option

MCA

1

(Amps)

Max Fuse

2

/

Breaker

3

Size

(Amps)

RLA LRA MCC

FLA

FLA

FLA

Model

kW

Stages

Amps