beautypg.com

Supply fan data – York ECO HFC-410A User Manual

Page 23

background image

FORM 100.50-EG5 (108)

23

JOHNSON CONTROLS

Supply Fan Data

TABLE 12 – 28" x 28" FORWARD-CURVED FAN

Total Static Pressure (inches of water column)

CFM

STD. AIR

1.0

2.0

3.0

4.0

5.0

6.0

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

12000

12.3

639

16.8

730

21.5

808

26.4

879

14000

14.3

642

19.2

738

24.3

818

29.7

890

16000

10.8

528

16.2

642

21.8

742

27.3

826

33.2

900

18000

12.7

537

18

643

24.4

742

30.6

829

36.8

906

20000

10.4

447

15

550

20.3

648

26.8

742

33.9

830

40.8

908

22000

12.9

471

17.6

566

23.3

657

29.4

745

36.9

830

24000

15.7

496

20.8

586

26.8

700

33

752

40

832

26000

19.1

522

24.5

607

30.5

686

37.3

762

TABLE 13 – 28" AIRFOIL FAN

Total Static Pressure (inches of water column)

CFM

STD. AIR

1.0

2.0

3.0

4.0

5.0

6.0

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

12000

12.6

1133

15.9

1241

19.5

1343

14000

5.2

806

8.1

947

11.4

1068

14.8

1177

18.4

1278

22.1

1374

16000

6.8

877

10

1011

13.5

1125

17.3

1228

21.2

1324

25.2

1415

18000

8.7

951

12.3

1077

16

1186

20.1

1285

24.3

1376

28.7

1462

20000

10.9

1027

15

1146

19

1251

23.3

1345

27.9

1433

32.6

1515

22000

13.6

1105

18.1

1218

22.4

1318

26.9

1409

31.8

1493

36.8

1572

24000

16.6

1184

21.7

1291

26.5

1387

31.2

1474

36.2

1556

26000

20.2

1265

25.7

1366

31

1457

36.1

1542