York SPLIT-SYSTEM YHJF18 THRU 60 User Manual
Page 26
Subject to change without notice. Published in U.S.A.
510667-YTG-B-0509
Copyright © 2009 by Johnson Controls, Inc. All rights reserved.
Supersedes: 510667-YTG-A-0409
Johnson Controls Unitary Products
5005 York Drive
Norman, OK 73069
Multipliers for determining the performance with other indoor sections.
HEATING PERFORMANCE DATA
CONDENSING UNIT MODEL NO
YHJF60S41S1
EVAPORATOR COIL MODEL NO
AHX60
AIR TEMP.
ENTERING
OUTDOOR UNIT
AIR TEMP.
ENTERING
INDOOR COIL
ID CFM
1600
1800
2000
MBTUH
KW
C.O.P.
MBTUH
KW
C.O.P.
MBTUH
KW
C.O.P.
60
60
70.70
4.28
4.25
71.76
4.41
4.11
72.83
4.54
3.97
70
69.78
3.85
4.72
70.63
3.95
4.57
71.49
4.07
4.41
80
68.86
3.48
5.19
69.51
3.58
5.03
70.15
3.67
4.86
47
60
61.77
3.89
4.05
62.15
3.97
3.92
62.54
4.05
3.78
70
60.84
3.47
4.53
61.18
3.55
4.39
61.52
3.62
4.23
80
59.90
3.13
5.01
60.20
3.19
4.86
60.50
3.27
4.69
40
60
56.20
3.64
3.93
56.47
3.70
3.80
56.74
3.76
3.69
70
55.47
3.24
4.42
55.62
3.30
4.27
55.76
3.35
4.13
80
54.75
2.92
4.90
54.77
2.96
4.75
54.79
3.02
4.57
30
60
49.33
3.30
3.78
49.52
3.33
3.70
49.72
3.34
3.61
70
47.84
2.83
4.36
47.68
2.87
4.21
47.52
2.90
4.06
80
46.36
2.45
4.94
45.84
2.49
4.71
45.31
2.53
4.51
17
60
40.18
2.78
3.64
37.45
2.80
3.50
34.72
2.80
3.40
70
40.02
2.47
4.14
38.68
2.60
4.00
37.36
2.50
3.91
80
39.86
2.23
4.65
39.91
2.25
4.53
39.99
2.27
4.42
10
60
35.02
2.49
3.52
35.29
2.51
3.45
35.54
2.53
3.38
70
33.76
2.16
3.98
34.56
2.22
3.90
35.35
2.27
3.82
80
32.50
1.89
4.44
33.83
1.97
4.34
35.15
2.06
4.26
NOTE: ALL CAPACITIES ARE NET (KBTUH) WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.
Air Handler
Coil
MBH
KW
COP
MV20D
FC/MC62D
0.99
1.00
0.99
Furnace
Coil
MBH
KW
COP
T*(8,L)X*C20
FC/MC62D
0.97
0.89
1.10
T*9X*C20
FC/MC62D
1.00
1.01
1.00
T*9X*D20
FC/MC62D
1.00
1.02
0.99
Y*(8,L)C*C20
FC/MC62D
0.99
0.95
1.04
(Y*9C/T*9V)*C20
FC/MC62D
0.99
0.96
1.04
(Y*9C/T*9V)*D20
FC/MC62D
1.00
0.97
1.03