York SPLIT-SYSTEM YHJF18 THRU 60 User Manual
Page 25
510667-YTG-B-0509
Johnson Controls Unitary Products
25
Multipliers for determining the performance with other indoor sections.
HEATING PERFORMANCE DATA
CONDENSING UNIT MODEL NO
YHJF48S41S1
EVAPORATOR COIL MODEL NO
F6FP060
AIR TEMP.
ENTERING
OUTDOOR UNIT
AIR TEMP.
ENTERING
INDOOR COIL
ID CFM
1400
1600
1800
MBTUH
KW
C.O.P.
MBTUH
KW
C.O.P.
MBTUH
KW
C.O.P.
60
60
62.2
4.3
3.7
62.7
4.5
3.5
63.2
4.6
3.3
70
60.9
3.8
4.2
61.2
3.9
4.0
61.6
4.1
3.8
80
59.5
3.3
4.8
59.8
3.5
4.5
60.0
3.6
4.2
47
60
53.1
3.6
3.8
53.1
3.7
3.6
53.1
3.8
3.4
70
52.0
3.2
4.3
52.0
3.2
4.1
52.1
3.3
3.9
80
50.9
2.8
4.8
51.0
2.9
4.6
51.0
2.9
4.5
40
60
47.9
3.2
3.8
47.8
3.3
3.6
47.8
3.4
3.4
70
47.2
2.8
4.4
47.0
2.9
4.2
46.9
3.0
3.9
80
46.5
2.5
5.0
46.2
2.6
4.7
45.9
2.6
4.4
30
60
40.1
2.9
3.6
40.2
2.9
3.5
40.3
2.9
3.3
70
38.9
2.7
3.8
39.3
2.7
3.8
39.6
2.6
3.7
80
37.8
2.5
4.0
38.3
2.4
4.0
38.8
2.4
4.1
17
60
30.2
2.6
2.8
31.3
2.8
2.8
32.4
2.9
2.7
70
28.7
2.4
3.0
29.5
2.4
3.0
30.3
2.5
2.9
80
27.3
2.2
3.2
27.7
2.2
3.2
28.1
2.2
3.1
10
60
25.2
2.4
2.6
24.8
2.3
2.5
24.4
2.3
2.5
70
24.5
2.1
2.9
25.3
2.1
3.0
26.1
2.0
3.2
80
23.8
1.9
3.1
25.7
1.8
3.5
27.7
1.8
3.9
NOTE: ALL CAPACITIES ARE NET (KBTUH) WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.
Air Handler
Coil
MBH
KW
COP
AHX60
–
1.00
0.99
1.01
MV20D
FC/MC62D
1.00
0.99
1.01
Furnace
Coil
MBH
KW
COP
T*(8,L)X*C16
FC/MC62D
1.00
0.98
1.02
T*(8,L)X*C20
FC/MC62D
1.00
0.99
1.01
T*9X*C16
FC/MC62D
1.00
0.98
1.02
T*9X*C20
FC/MC62D
1.00
0.99
1.01
T*9X*D20
FC/MC62D
1.00
0.98
1.02
Y*(8,L)C*C16
FC/MC62D
1.00
0.98
1.02
Y*(8,L)C*C20
FC/MC62D
1.00
0.98
1.02
(Y*9C/T*9V)*C16
FC/MC62D
1.00
0.97
1.03
(Y*9C/T*9V)*C20
FC/MC62D
1.00
0.96
1.04
(Y*9C/T*9V)*D20
FC/MC62D
1.00
0.97
1.03