York SPLIT-SYSTEM YHJF18 THRU 60 User Manual
Page 18
510667-YTG-B-0509
18
Johnson Controls Unitary Products
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed
temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
LOW CFM
COOLING PERFORMANCE DATA - LOW CFM 1-STAGE OPERATION
CONDENSING UNIT MODEL NO. YHJF60S41S1
INDOOR COIL MODEL NO.
AHX60
CONDENSING
ENTERING AIR
TEMPERATURE
IDCFM
965
1165
1365
ID
DB
(°F)
80 80
75
80
80
80 80 75
80
80 80 80
75 80 80
ID
WB
(°F)
57 62 62 67 72 57 62 62 67 72 57 62 62 67 72
65
T.C.
37.3
41.8
41.6
45.5
50.9
40.4
43.7
43.3
47.7
52.2
43.5
45.6
45.1
49.9
53.6
S.C.
35.2
32.0
27.8
27.8
23.7
38.1
35.1
30.0
30.0
24.9
41.1
38.2
32.2
32.3
26.1
KW
2.1
2.1
2.1
2.1
2.1
2.2
2.2
2.2
2.2
2.2
2.3
2.3
2.3
2.3
2.3
75
T.C.
36.2
39.9
39.8
43.6
48.4
39.0
41.6
41.3
45.5
49.8
41.8
43.3
42.8
47.4
51.2
S.C.
34.2
31.2
27.0
27.0
22.7
36.8
34.3
29.1
29.1
23.9
39.5
37.3
31.3
31.3
25.1
KW
2.4
2.4
2.4
2.4
2.4
2.5
2.5
2.5
2.5
2.5
2.6
2.6
2.6
2.6
2.6
85
T.C.
35.2
38.0
37.9
41.8
46.0
37.6
39.4
39.2
43.3
47.4
40.1
40.9
40.5
44.8
48.8
S.C.
33.2
30.5
26.1
26.1
21.7
35.5
33.5
28.3
28.3
22.9
37.8
36.5
30.4
30.4
24.0
KW
2.7
2.7
2.8
2.7
2.8
2.8
2.8
2.8
2.8
2.8
2.9
2.9
2.9
2.9
2.9
95
T.C.
34.1
36.0
36.0
39.9
43.6
36.2
37.3
37.1
41.1
45.0
38.3
38.5
38.2
42.3
46.5
S.C.
32.2
29.7
25.3
25.3
20.7
34.2
32.7
27.4
27.4
21.9
36.2
35.7
29.5
29.4
23.0
KW
3.1
3.1
3.1
3.1
3.1
3.1
3.1
3.1
3.1
3.1
3.2
3.2
3.2
3.2
3.2
105
T.C.
32.4
33.7
33.7
37.3
40.9
34.2
34.7
34.6
38.3
42.1
36.1
35.7
35.5
39.3
43.3
S.C.
30.6
28.8
24.3
24.3
19.6
32.3
31.1
26.4
26.3
20.8
34.1
33.3
28.5
28.4
22.0
KW
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.6
3.6
3.6
3.6
3.6
115
T.C.
30.6
31.4
31.4
34.7
38.3
32.3
32.1
32.1
35.5
39.2
33.9
32.8
32.8
36.3
40.1
S.C.
28.9
27.8
23.3
23.2
18.6
30.5
29.4
25.4
25.3
19.7
32.0
31.0
27.4
27.3
20.9
KW
3.9
3.9
3.9
3.9
3.9
3.9
3.9
3.9
3.9
3.9
4.0
4.0
4.0
4.0
4.0
125
T.C.
28.9
29.1
29.1
32.1
35.7
30.3
29.5
29.6
32.7
36.3
31.7
29.9
30.1
33.4
37.0
S.C.
27.3
26.9
22.4
22.2
17.5
28.6
27.8
24.4
24.2
18.7
30.0
28.6
26.4
26.3
19.9
KW
4.3
4.3
4.3
4.3
4.3
4.3
4.3
4.3
4.3
4.4
4.4
4.4
4.4
4.4
4.4
NOTE: ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH/1000 CFM.
Air Handler
Coil
T.C.
S.C.
KW
MV20D
FC/MC62D
1.00
1.00
0.99
Furnace
Coil
T.C.
S.C.
KW
T*(8,L)X*C20
FC/MC62D
0.92
0.87
0.97
T*9X*C20
FC/MC62D
1.01
1.02
1.02
T*9X*D20
FC/MC62D
1.02
1.03
1.01
Y*(8,L)C*C20
FC/MC62D
0.97
0.94
0.99
(Y*9C/T*9V)*C20
FC/MC62D
0.97
0.95
1.00
(Y*9C/T*9V)*D20
FC/MC62D
0.98
0.96