TABLE 11: STATIC RESISTANCES

TABLE 12: ELECTRIC HEATER CFM LIMITATIONS

1000

1200

1400

1600

1800

2000

2200

2400

2600

2800

3000

0.07

0.08

0.09

0.11

0.13

0.15

0.17

0.20

0.23

0.26

0.30

7-15KW

0.04

0.05

0.06

0.07

0.08

0.10

0.12

0.14

0.16

0.19

0.22

20-30KW

0.06

0.07

0.08

0.09

0.11

0.13

0.15

0.17

0.20

0.23

0.26

0.06

0.07

0.08

0.09

0.10

0.11

0.12

0.14

0.16

0.19

0.22

0.08

0.10

0.12

0.14

0.16

0.18

0.20

0.23

0.26

0.29

0.32

COOLING ONLY

2

RESISTANCE, IWG

CFM

DESCRIPTION

ECONOMIZER

1 3

BOTTOM DUCT CONNECTIONS

1

ELECTRIC

HEATERS

1

1. Deduct these resistance values from the available external static pressure shown in SUPPLY AIR BLOWER PERFORMANCE Tables.

3. The pressure through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return air
duct system is less than 0.25 IWG, the unit will deliver less CFM during full economizer operation.

2. Add these resistance values to the available static resistance values on SUPPLY AIR BLOWER PERFORMANCE Tables.

5

7

10

15

20

30

208/230-1-60

1100

1100

1200

1200

1300

-

208/230-3-60

1100

1100

1200

1200

1300

-

460-3-60

-

1100

1200

1200

1300

-

575-3-60

-

-

1200

1200

1300

-

208/230-1-60

1300

1300

1300

1300

1300

-

208/230-3-60

1300

1300

1300

1300

1300

-

460-3-60

-

1300

1300

1300

1300

-

575-3-60

-

-

1300

1300

1400

-

208/230-1-60

1600

1600

1600

1600

1600

1600

208/230-3-60

1600

1600

1600

1600

1600

1600

460-3-60

-

1600

1600

1600

1600

1600

575-3-60

-

-

1600

1600

1600

1800

3

4

5

MINIMUM SUPPLY AIR CFM

HEATER SIZE NOMINAL KW

VOLTAGE

UNIT MODEL SIZE NOMINAL

TONS