beautypg.com

York DH 036 User Manual

Page 15

background image

036-21506-003-C-0405

Unitary Products Group

15

TABLE 1: SOUND POWER RATING

1

UNIT

SIZE

CFM

ESP

BLOWER

SOUND POWER (db 10

-12

Watts)

Octave Band Centerline Frequency (Hz)

SWL

dB(A)

dB(A)

@

10Ft.

2

IWG

SPEED

KW

63

125

250

500

1,000

2,000

4,000

8,000

036

1,200

0.6

LOW

0.60

84

84

74

67

69

62

57

52

74

41

048

1,600

0.55

HIGH

0.80

85

85

75

68

70

63

58

53

75

42

060

2,000

0.45

HIGH

1.00

86

86

76

69

71

64

59

54

76

43

1. These values have been accessed using a model of sound propagation from a point source into the hemispheric\free field. The

dBA values provided are to be used for reference only. Calculation of dBA values cover matters of system design and the fan
manufacture has no way of knowing the details of each system. This constitutes and expectation to any specification or guaran-
tee requiring a dBA value or sound data in any other form than sound power level ratings.

2. At a distance of 10 feet from the blower.

TABLE 2: CAPACITY RATINGS - (ARI 210/240)

1

1. 80/67°F Indoor and 95°F outdoor.

MODEL

MBH

EER

2

2. EER = Energy Efficiency Ratio at full load - the cooling

capacity in Btu’s per hour (Btuh) divided by the power
input in watts, expressed in Btuh per watt (Btuh/watt).

SEER

3

3. SEER = Seasonal Energy Efficiency Ratio.

DH036

42.5

11.1

12.25

DH048

46.5

11.4

13.20

DH060

57.0

10.6

12.20

TABLE 3: GAS HEAT RATINGS

1

1. All units are single-stage heating.

MODEL

MBH

INPUT

MBH

OUTPUT

AFUE

(%)

TEMP

RISE ºF

DH036N04
DH036N08

50

100

40
79

80.9
80.5

15 - 45
40 - 70

DH048N06
DH048N10

75

125

59
99

80.9
80.3

25 - 55
45 - 75

DH060N08
DH060N10

100
125

79
99

80.5
80.3

25 - 55
35 - 65