Table 11: electric heat multipliers – York PREDATORTM MAGNUM DJ 150 User Manual
Page 13
![background image](/manuals/227883/13/background.png)
036-21484-001-B-0103
Unitary Products
13
NOTE: Electric heaters are rated at nominal voltage. Use this
table to determine the electric heat capacity for heaters sup-
plied at lower voltages.
NOTES FOR TABLES 12 AND TABLE 13:
•
Blower performance includes dry coil and 2” throwaway
filters.
•
Blower performance for gas heat includes the maximum
number of heat tubes available for each tonnage.
ESP (External Static Pressure) given is that available for the
supply and return air duct system. All internal resistances
have been deducted from the total static pressure of the
blower.
TABLE 10: DJ 150 (12-1/2 TON) - ELECTRICAL DATA
Model
Compressors
OD Fan
Motors
Motor,
Supply
Blowe
FLA
Pwr
Exh
Motor
Electric Heater
Model
No.
Rated
kW
Minimum Circuit
Ampacity
Amps
MCA
with
Power
Exhaust Amps
Max Fuse
Size
* Amps
Max Fuse
Size
w/ Pwr. Exh. * Amps
Tonnage Voltage RLA each LRA each FLA each 3 HP 5 HP
FLA
3 HP
5 HP
3 HP
5 HP
3 HP 5 HP
3 HP
5 HP
12 1/2
208
20.0
146
1.5
10.9 16.1
5.5
None
-
61.9
67.1
67.4
72.6
80
80
80
90
2TP04511825
13.5
61.9
67.1
67.4
73.8
80
80
80
90
2TP04512425
18.0
76.1
82.6
83.0
89.5
80
90
90
90
2TP04513625
25.5
102.1
108.6
109.0
115.5
110
110
110
125
2TP04515425
40.6
154.5
161.0
161.4
167.9
175
175
175
175
230
20.0
146
1.5
10.9 16.1
5.5
None
-
61.9
67.1
67.4
72.6
80
80
80
90
2TP04511825
18.0
67.8
74.3
74.6
81.1
80
80
80
90
2TP04512425
24.0
85.8
92.3
92.7
99.2
90
100
100
100
2TP04513625
34.0
115.9
122.4
122.7
129.2
125
125
125
150
2TP04515425
54.0
143.5
150.0
150.4
156.9
175
175
175
175
460
8.4
73
0.8
5.3
8.1
2.2
None
-
27.4
30.2
29.6
32.4
35
35
35
40
2TP04511846
18.0
33.7
37.2
36.4
39.9
35
40
40
40
2TP04512446
24.0
42.7
46.2
45.5
49.0
45
50
50
50
2TP04513646
34.0
57.7
61.2
60.5
64.0
60
70
70
70
2TP04515446
54.0
71.6
75.1
74.3
77.8
80
90
80
90
575
6.7
60
0.6
4.1
6.0
1.8
None
-
21.6
23.5
23.4
25.3
25
30
30
30
2TP04511858
18.0
26.8
29.2
29.0
31.4
30
30
30
35
2TP04512458
24.0
34.0
36.4
36.2
38.6
35
40
40
40
2TP04513658
34.0
46.0
48.4
48.3
50.6
50
50
50
60
2TP04515458
54.0
57.1
59.5
59.3
61.7
70
70
70
70
TABLE 11: ELECTRIC HEAT MULTIPLIERS
VOLTAGE
kW Cap. Multiplier
NOMINAL
RATING
240
208
0.75
230
0.92
480
460
0.92
600
575
0.92