beautypg.com

York PREDATORTM MAGNUM DJ 150 User Manual

Page 11

background image

036-21484-001-B-0103

Unitary Products

11

TABLE 7: DJ 150 (12-1/2 TON) CAPACITY RATINGS

Size

(Tons)

Model

Cooling Capacity

ARI Ratings

*

CFM

Sound

Rating

(dB)

Nominal

Electric

Heat

Capacity

(kW)

Gas Heat Capacity

Gas

Line
Size

(in. OD)

MBH

EER

IPLV

Input

(MBH)

Output

(MBH)

Seasonal

Efficiency (%)

Temp.

Rise (°F)

150

(12-1/2)

Cooling

Only

144

10.8

11.2

3750

86

-

-

-

-

-

-

Electric

Heat

18, 24, 36

54

-

-

-

-

-

Gas Heat

-

180

144

80

10-40

3/4

Gas Heat

-

240

192

80

25-55

3/4

*

Rated at 95°F ambient 80°F dry bulb and 67°F wet bulb.

Rated in accordance with ARI 270 standard.

See Table 11.

TABLE 8: UNIT VOLTAGE LIMITATIONS

POWER RATING

MIN.

MAX.

208/230-3-60

187

252

460-3-60

432

504

575-3-60

540

630