Table 1: general data – York 359583-YTG-B-0208 User Manual
Page 3
![background image](/manuals/227802/3/background.png)
359583-YTG-B-0208
Johnson Controls Unitary Products
3
NOTE:
1.
Performance calculated in accordance with ARI/ISO Standard 13256-1 for Water Loop Application.
2.
Cooling capacities are rated at entering air conditions of 80.6ºF db / 66.2ºF wb. 86ºF entering water temperature.
3.
Heating capacities are rated at entering air conditions of 68ºF db / 59ºF wb, 68ºF entering water temperature.
TABLE 1: GENERAL DATA
Model Series
007
009
012
018
024
030
036
048
060
Nominal Cooling (Ton)
0.5
0.75
1.0
1.5
2.0
2.5
3.0
4.0
5.0
Cooling Performance
Cooling Capacity (BTUH)
7000
9000
12800
18100
24200
30800
36100
48200
59000
EER
12.4
13.0
12.6
14.4
14.4
13.5
14.2
14.0
12.6
Heating Capacity (BTUH)
8800
10700
14800
20900
27500
35200
41400
56000
72000
COP
4.2
4.4
4.2
4.5
4.6
4.4
4.6
4.6
4.4
Design CFM
200
300
400
600
800
1000
1200
1600
2000
Nominal Waterflow (gpm)
1.5
2.25
3.0
4.5
6.0
7.5
9.0
12.0
15.0
Compressor-Type
Rotary
Rotary
Rotary
Recip.
Recip.
Recip.
Recip.
Recip.
Recip.
Number Used
1
1
1
1
1
1
1
1
1
Air Coil- Type
Enhanced Copper Tubes, Enhanced Aluminum Fins
Face Area (sq. Ft.)
1.00
1.00
1.00
1.51
2.56
2.56
2.88
4.38
5.00
Rows/FPI
2/14
2/14
3/14
3/14
3/14
3/14
3/14
3/14
3/14
Water Coil - Type
Co-Axial
Water Connection Size
1/2” FPT
1/2” FPT
1/2” FPT
3/4” FPT
3/4” FPT
3/4” FPT
3/4” FPT
3/4” FPT
1” FPT
Drain Connection Size
3/4” FPT
Direct Drive Fan-Type
Centrifugal, Forward Curved
Number Used
1
1
1
1
1
1
1
1
1
Diameter x Width (in)
9x4
9x4
9x4
9x6
9x7
9x7
9x7
10x9
10x9
Motor HP /Speed
0.10/3
0.10/3
0.17/3
0.25/3
0.25/3
0.33/3
0.50/3
0.75/3
1.0/3
Filters
Horizontal Model - Qty. Size
1-14x16x1
1-14x16x1
1-14x16x1
1-16x20x1
1-18x25x1
1-18x25x1
1-20x25x1
2-20x20x1
1-20x20x1
1-20x25x1
Vertical Models - Qty. Size
1-14x16x1
1-14x16x1
1-14x16x1
1-16x20x1
1-18x25x1
1-18x25x1
1-20x25x1
1-16x25x1
1-14x25x1
1-18x25x1
1-16x25x1
Weight
Operating
130
135
155
180
215
235
260
325
345
Shipping
145
150
170
195
230
255
280
345
365
OPERATING LIMITS - WATER LOOP APPLICATION
Cooling
Heating
Min. Entering Water
50ºF
40ºF
*
Max. Entering Water
110ºF
80ºF
Normal Entering Water
60-90ºF
50-70ºF
*.
Heating operation below 55ºF requires insulated water circuit.