beautypg.com

Air flow correction factors – York 359583-YTG-B-0208 User Manual

Page 12

background image

359583-YTG-B-0208

12

Johnson Controls Unitary Products

NOTE: All capacity data shown is NET - includes motor power/heat at design
CFM and HI fan speed. Tabulated kW values do not include allowance for
external pumping power.

TABLE 10: RP 060 @ 2000 CFM NOMINAL AIRFLOW VERTICAL AND HORIZONTAL MODELS

EWT

(ºF)

GPM

WPD
(PSI)

Cooling

EWT(ºF)

GPM

Heating

EAT

(db/wb)

TC

(MBH)

SC

(MBH)

KW

THR

(MBH)

EAT

(db)

HC

(MBH)

KW

H Absrp.

(MBH)

50

75/62

61.7

48.4

3.82

74.7

50

60

52.0

3.88

38.7

9.0

3.6

80/67

68.1

48.1

3.91

81.4

9.0

70

51.3

4.13

37.2

85/72

75.0

47.6

4.03

88.7

80

50.8

4.38

35.9

75/62

63.0

49.0

3.66

75.5

60

56.9

4.05

43.1

15.0

8.8

80/67

69.5

48.6

3.74

82.2

15.0

70

56.1

4.32

41.4

85/72

76.5

48.1

3.85

89.6

80

55.6

4.59

39.9

60

75/62

59.4

47.5

4.08

73.3

60

60

59.0

4.12

45.0

9.0

3.5

80/67

65.7

47.2

4.17

79.9

9.0

70

58.2

4.39

43.2

85/72

72.0

46.6

4.34

86.8

80

57.6

4.66

41.6

75/62

60.7

48.0

3.94

74.1

60

66.1

4.36

51.2

15.0

8.5

80/67

67.1

47.7

4.02

80.8

15.0

70

65.1

4.65

49.2

85/72

73.5

47.1

4.18

87.7

80

64.3

4.94

47.4

70

75/62

56.4

46.2

4.39

71.4

70

60

77.0

4.45

61.8

9.0

3.3

80/67

62.8

46.1

4.47

78.0

9.0

70

75.6

4.75

59.4

85/72

69.3

45.6

4.60

85.0

80

74.5

5.05

57.3

75/62

58.1

46.9

4.22

72.5

60

76.1

4.70

60.1

15.0

8

80/67

64.3

46.6

4.32

79.0

15.0

70

74.8

5.02

57.7

85/72

71.2

46.3

4.40

86.2

80

73.8

5.34

55.6

85

75/62

52.4

44.6

4.87

69.0

80

60

77.8

4.76

61.5

9.0

3.1

80/67

57.7

44.1

4.95

74.6

9.0

70

76.4

5.08

59.1

85/72

63.5

43.7

5.12

80.9

80

75.4

5.40

57.0

75/62

53.8

45.1

4.66

69.7

60

87.0

5.09

69.6

15.0

7.6

80/67

58.9

44.6

4.84

75.4

15.0

70

85.5

5.44

66.9

85/72

65.5

44.3

5.22

83.3

80

84.3

5.79

64.5

100

75/62

47.7

42.6

5.21

65.5

9.0

3.0

80/67

52.4

42.2

5.42

70.9

85/72

58.5

42.1

5.57

77.5

75/62

49.1

43.2

5.09

66.4

15.0

7.3

80/67

54.6

43.0

5.23

72.4

85/72

60.4

42.7

5.38

78.7

TC = TOTAL COOLING CAPACITY
SC = SENSIBLE COOLING CAPACITY
THR = TOTAL HEAT REJECTION
HC = TOTAL HEATING CAPACITY
WPD = WATER PRESSURE DROP

AIR FLOW CORRECTION FACTORS

AIRFLOW

HEATING

COOLING

%

OF

Nominal

CFM

HC

Input

Power

Heat

Absrp.

TC

SC

Input

Power

THR

80

1600

0.986

1.058

0.969

0.966

0.893

0.992

0.971

90

1800

0.993

1.029

0.985

0.983

0.947

0.996

0.986

100

2000

1.000

1.000

1.000

1.000

1.000

1.000

1.000

110

2200

1.007

0.977

1.014

1.011

1.049

1.004

1.011

115

2300

1.010

0.965

1.021

1.017

1.074

1.006

1.016