Air flow correction factors – York 359583-YTG-B-0208 User Manual
Page 12
359583-YTG-B-0208
12
Johnson Controls Unitary Products
NOTE: All capacity data shown is NET - includes motor power/heat at design
CFM and HI fan speed. Tabulated kW values do not include allowance for
external pumping power.
TABLE 10: RP 060 @ 2000 CFM NOMINAL AIRFLOW VERTICAL AND HORIZONTAL MODELS
EWT
(ºF)
GPM
WPD
(PSI)
Cooling
EWT(ºF)
GPM
Heating
EAT
(db/wb)
TC
(MBH)
SC
(MBH)
KW
THR
(MBH)
EAT
(db)
HC
(MBH)
KW
H Absrp.
(MBH)
50
75/62
61.7
48.4
3.82
74.7
50
60
52.0
3.88
38.7
9.0
3.6
80/67
68.1
48.1
3.91
81.4
9.0
70
51.3
4.13
37.2
85/72
75.0
47.6
4.03
88.7
80
50.8
4.38
35.9
75/62
63.0
49.0
3.66
75.5
60
56.9
4.05
43.1
15.0
8.8
80/67
69.5
48.6
3.74
82.2
15.0
70
56.1
4.32
41.4
85/72
76.5
48.1
3.85
89.6
80
55.6
4.59
39.9
60
75/62
59.4
47.5
4.08
73.3
60
60
59.0
4.12
45.0
9.0
3.5
80/67
65.7
47.2
4.17
79.9
9.0
70
58.2
4.39
43.2
85/72
72.0
46.6
4.34
86.8
80
57.6
4.66
41.6
75/62
60.7
48.0
3.94
74.1
60
66.1
4.36
51.2
15.0
8.5
80/67
67.1
47.7
4.02
80.8
15.0
70
65.1
4.65
49.2
85/72
73.5
47.1
4.18
87.7
80
64.3
4.94
47.4
70
75/62
56.4
46.2
4.39
71.4
70
60
77.0
4.45
61.8
9.0
3.3
80/67
62.8
46.1
4.47
78.0
9.0
70
75.6
4.75
59.4
85/72
69.3
45.6
4.60
85.0
80
74.5
5.05
57.3
75/62
58.1
46.9
4.22
72.5
60
76.1
4.70
60.1
15.0
8
80/67
64.3
46.6
4.32
79.0
15.0
70
74.8
5.02
57.7
85/72
71.2
46.3
4.40
86.2
80
73.8
5.34
55.6
85
75/62
52.4
44.6
4.87
69.0
80
60
77.8
4.76
61.5
9.0
3.1
80/67
57.7
44.1
4.95
74.6
9.0
70
76.4
5.08
59.1
85/72
63.5
43.7
5.12
80.9
80
75.4
5.40
57.0
75/62
53.8
45.1
4.66
69.7
60
87.0
5.09
69.6
15.0
7.6
80/67
58.9
44.6
4.84
75.4
15.0
70
85.5
5.44
66.9
85/72
65.5
44.3
5.22
83.3
80
84.3
5.79
64.5
100
75/62
47.7
42.6
5.21
65.5
9.0
3.0
80/67
52.4
42.2
5.42
70.9
85/72
58.5
42.1
5.57
77.5
75/62
49.1
43.2
5.09
66.4
15.0
7.3
80/67
54.6
43.0
5.23
72.4
85/72
60.4
42.7
5.38
78.7
TC = TOTAL COOLING CAPACITY
SC = SENSIBLE COOLING CAPACITY
THR = TOTAL HEAT REJECTION
HC = TOTAL HEATING CAPACITY
WPD = WATER PRESSURE DROP
AIR FLOW CORRECTION FACTORS
AIRFLOW
HEATING
COOLING
%
OF
Nominal
CFM
HC
Input
Power
Heat
Absrp.
TC
SC
Input
Power
THR
80
1600
0.986
1.058
0.969
0.966
0.893
0.992
0.971
90
1800
0.993
1.029
0.985
0.983
0.947
0.996
0.986
100
2000
1.000
1.000
1.000
1.000
1.000
1.000
1.000
110
2200
1.007
0.977
1.014
1.011
1.049
1.004
1.011
115
2300
1.010
0.965
1.021
1.017
1.074
1.006
1.016