7

66297-YIM-C-0205

TABLE 5 - ELECTRICAL DATA (12 SEER HEAT PUMP / ELECTRIC HEAT) (Continued)

MODEL

BHH

POWER

SUPPLY

COMPRESSOR

COND.

FAN

MOTOR

FLA

SUPPLY

AIR

BLOWER

MOTOR,

FLA

ELECTRIC HEAT ACCESSORY

MINIMUM

CIRCUIT

AMPACITY

MAX.

FUSE

SIZE,

1

AMPS

MAX.

HACR

2

BREAKER

SIZE

RLA

LRA

MODEL

NO.

KW

TOTAL

AMPS

036

575-3-60

4.7

32.0

0.4

1.5

2NH04501058
2NH04501558

10.0***
15.0***

9.6

14.4

19.8
25.8

20
30

20
20

042

575-3-60

5.4

34.0

0.4

1.5

2NH04501058
2NH04501558

10.0***
15.0***

9.6

14.4

20.7
26.7

25
30

25
30

048

575-3-60

5.1

37.2

0.6

1.6

2NH04501058
2NH04501558
2NH04502058
2NH04502558

10.0***
15.0***
20.0***
25.0***

9.6

14.4
19.2
24.1

20.6
26.7
32.7
38.7

25
30
35
40

25
30
35
40

060

575-3-60

7.0

50.0

0.6

2.8

2NH04501058
2NH04501558
2NP04502058
2NP04502558

10.0***
15.0***
20.0***
25.0***

9.6

14.4
19.2
24.1

24.2
30.2
36.3
42.3

25
35
40
45

25
35
40
45

1

= Dual element, time delay type.

* = KW listed is for 240 volts, use table on previous page for 208 or 230 volts.

2

= Standard circuit breakers may be used in Canada and on applications ** = KW listed is for 480 volts, use table on previous page for 460 volts.

over 60 amps where the heaters are separately fused. *** = KW listed is for 600 volts, use table on previous page for 575 volts.

This manual is related to the following products: