Install the bracket on the left hand side of the unit as shown in

Figure 5. Several existing screws at the top of the unit and one

screw approximately midway down from the top will be used for

mounting the bracket. Screws should be loosened only - NOT

REMOVED. Matching holes in the bracket have elongated

keyways allowing easy installation. Re-tighten screws after

bracket is in place to ensure panels will remain leak tight.

ELECTRIC HEATERS

Electric heaters are available as field-installed accessories.

Refer to Form 530.18-N7.1V for installation instruction. These

UL approved heaters are located within the central

compartment of the unit (see Figure 5 for access panel) with

the heating elements extending into the supply air chamber.

The heaters are wired for a single point power supply. Power

supply need only be brought into the single point terminal block

035-12046-003-A-0204

8

Unitary Products Group

FIG. 6 - ENTHALPY SET POINT ADJUSTMENT

TABLE 3 - SUPPLY AIR PERFORMANCE - 3 THRU 5 TON w/Direct-Drive Blower

UNIT

SIZE

(MBH)

MOTOR

SPEED

Available External Static Pressure - IWG*

0.20

0.30

0.40

0.50

0.60

0.70

0.80

0.90

1.00

CFM Watts CFM Watts CFM Watts CFM Watts CFM Watts CFM Watts CFM Watts CFM Watts CFM Watts

036

HI

MED

LOW

-

1684

1487

-

800

710

-

1631

1464

-

780

690

1699

1582

1421

825

750

670

1650

1524

1367

785

720

650

1570

1410

1315

755

690

620

1430

1324

1246

725

650

605

1360

1260

1185

700

630

590

1280

1185

1110

680

610

570

1180

1100

1020

655

590

545

048

HI

MED

LOW

1996

1804

1681

960

838

760

1933

1765

1640

936

810

738

1868

1714

1604

910

785

715

1795

1650

1541

880

765

695

1722

1589

1490

845

735

670

1635

1508

1416

820

705

645

1544

1407

1337

790

675

620

1419

1306

1230

765

645

595

1300

1195

1120

740

625

575

060

HI

MED

LOW

2400

2290

2150

1155

1105

1020

2338

2214

2100

1125

1065

990

2274

2145

2029

1095

1030

950

2167

2071

1965

1045

990

910

2096

1990

1905

1010

950

880

1990

1911

1816

980

920

838

1887

1828

1724

945

885

800

1771

1724

1644

905

835

770

1629

1604

1531

855

798

710

NOTE: FOR 208 VOLTS, MULTIPLY VALUES BY 0.95.

*

INCLUDES ALLOWANCES FOR A WET EVAPORATOR COIL, 1" FILTERS AND GAS-FIRED HEAT EXCHANGERS. REFER TO THE STATIC RESISTANCES TABLE FOR RESISTANCE

VALUES ON APPLICATIONS OTHER THAN GAS / ELECTRIC UNITS WITH SIDE DUCT AIRFLOWS.

GAS HEAT VALUES SHOWN @ 230/460/575 VOLTS - Side Duct Connections

This manual is related to the following products: