12

Unitary Products Group

Multipliers for determining the performance with other indoor sections.

NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the
listed temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.

COOLING PERFORMANCE DATA

AIR CONDITIONER MODEL NO.

AY018MA321

INDOOR COIL MODEL NO.

G2FD024S17

CONDENSER

ENTERING AIR

TEMPERATURE

ID CFM

450

600

750

ID DB (°F)

80

80

75

80

80

80

80

75

80

80

80

80

75

80

80

ID WB (°F)

57

62

62

67

72

57

62

62

67

72

57

62

62

67

72

65

T.C.

16.3

18.5

18.6

20.3

22.1

17.8

19.1

19.1

20.8

22.5

19.3

19.7

19.7

21.2

22.9

S.C.

15.4

14.0

12.3

12.1

9.8

17.0

15.8

13.8

13.4

10.9

18.6

17.7

15.3

14.8

12.1

KW

1.2

1.2

1.2

1.2

1.2

1.2

1.2

1.2

1.2

1.2

1.2

1.2

1.2

1.2

1.2

75

T.C.

15.9

17.5

17.6

19.3

21.3

17.3

18.2

18.2

19.9

21.7

18.6

18.8

18.9

20.4

22.1

S.C.

15.0

13.4

11.7

11.6

9.5

16.5

15.3

13.3

13.1

10.6

17.9

17.2

14.9

14.6

11.8

KW

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

1.3

85

T.C.

15.6

16.6

16.6

18.3

20.5

16.7

17.2

17.3

18.9

20.9

17.9

17.9

18.1

19.6

21.2

S.C.

14.7

12.9

11.1

11.1

9.3

16.0

14.7

12.8

12.7

10.3

17.3

16.6

14.4

14.4

11.4

KW

1.5

1.5

1.5

1.5

1.5

1.5

1.5

1.5

1.5

1.5

1.5

1.5

1.5

1.5

1.5

95

T.C.

15.2

15.6

15.6

17.3

19.7

16.2

16.3

16.4

18.0

20.0

17.2

17.0

17.3

18.7

20.4

S.C.

14.3

12.3

10.5

10.6

9.1

15.5

14.2

12.3

12.4

10.0

16.6

16.1

14.0

14.2

11.0

KW

1.6

1.6

1.6

1.6

1.6

1.6

1.6

1.6

1.6

1.6

1.6

1.6

1.6

1.6

1.6

105

T.C.

13.9

14.6

14.7

16.3

18.6

15.1

15.3

15.4

17.0

18.9

16.3

15.9

16.1

17.6

19.3

S.C.

13.0

11.8

10.0

10.2

8.6

14.2

13.4

11.6

11.9

9.6

15.4

15.0

13.3

13.7

10.7

KW

1.8

1.8

1.8

1.8

1.8

1.8

1.8

1.8

1.8

1.8

1.8

1.8

1.8

1.8

1.8

115

T.C.

12.7

13.7

13.7

15.3

17.5

14.0

14.3

14.4

15.9

17.8

15.3

14.9

15.0

16.6

18.2

S.C.

11.8

11.2

9.5

9.7

8.2

13.0

12.5

11.1

11.4

9.2

14.3

13.8

12.6

13.2

10.3

KW

1.9

1.9

1.9

2.0

2.0

2.0

2.0

2.0

2.0

2.0

2.0

2.0

2.0

2.0

2.0

125

T.C.

11.4

12.8

12.8

14.4

16.4

12.9

13.3

13.3

14.9

16.7

14.4

13.9

13.8

15.5

17.1

S.C.

10.5

10.7

9.0

9.2

7.7

11.8

11.7

10.5

11.0

8.9

13.2

12.7

11.9

12.7

10.0

KW

2.1

2.1

2.1

2.2

2.2

2.1

2.1

2.1

2.2

2.2

2.2

2.2

2.2

2.2

2.2

NOTE: ALL CAPACITIES ARE NET WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.

Air Handler

Coil

T.C.

S.C.

KW

MV12B

FC/MC18B

1.02

1.03

0.94

MV12B

G4FD024H17T2A

1.02

1.03

0.94

AHP18

1.00

1.00

1.00

AHP24

1.00

1.00

1.00

F4FP024H06T2A

1.00

1.00

1.00

FC/MC/PC18

1.00

1.00

1.00

G4FA030S14T2A

1.00

1.00

1.00

G4FA036S17T2A

1.00

1.00

1.00

G4FA036S21T2A

1.00

1.00

1.00

G4FD024H14T2A

1.00

1.00

1.00

G4FD024H17T2A

1.00

1.00

1.00

G4FD030H17T2A

1.00

1.00

1.00

G4FD035H14T2A

1.00

1.00

1.00

HC24

1.00

1.00

1.00

UC18

1.00

1.00

1.00

Variable Speed

Furnace

Coil

T.C.

S.C.

KW

PV8*A12

FC/MC/PC18A

1.02

1.03

0.94

PV8*B16

FC/MC/PC18B

1.02

1.03

0.94

PV9*A12

FC/MC/PC18A

1.02

1.02

0.97

PV9*B12

FC/MC/PC18B

1.02

1.03

0.94

PV8*B16

G4FA036S17T2A

1.02

1.03

0.94

PV9*B12

G4FA036S17T2A

1.02

1.03

0.94

PV8*A12

G4FA030S14T2A

1.02

1.03

0.94

PV9*A12

G4FA030S14T2A

1.02

1.02

0.97

PV8*A12

G4FD024H14T2A

1.02

1.03

0.94

PV9*A12

G4FD024H14T2A

1.02

1.02

0.97

PV8*B16

G4FD024H17T2A

1.02

1.03

0.94

PV9*B12

G4FD024H17T2A

1.02

1.03

0.94

PV8*B16

G4FD030H17T2A

1.02

1.03

0.94

PV9*B12

G4FD030H17T2A

1.02

1.03

0.94

PV8*A12

G4FD035H14T2A

1.02

1.03

0.94

PV8*B16

FC/MC/PC18B

1.02

1.03

0.94

PV9*A12

FC/MC/PC18A

1.02

1.02

0.97