York DM 060 User Manual
Page 24
036-21502-002-A-0303
24
Unitary Products Group
TABLE 18: ELECTRICAL DATA - DM036 & 048 BELT DRIVE WITHOUT POWR’D CONVENIENCE OUTLET
NONE
0.0
0.0
31.4
45
2CE04510506
4.0
19.2
33.5
45
2CE04510706
5.6
26.9
43.2
45
2CE04511006
8.0
38.5
57.6
60
2CE04511506
11.9
57.2
81.0
90
2CE04512006
15.9
76.4
105.1
110
NONE
0.0
0.0
31.4
45
2CE04510506
5.3
22.1
37.1
45
2CE04510706
7.5
31.3
48.6
50
2CE04511006
10.6
44.2
64.7
70
2CE04511506
15.9
66.3
92.3
100
2CE04512006
21.2
88.3
119.9
125
NONE
0.0
0.0
20.8
30
2CE04510525
2
4.0
11.1
20.8
30
2CE04510725
2
5.6
15.5
25.9
30
2CE04511025
8.0
22.2
34.3
35
2CE04511525
11.9
33.0
47.8
50
2CE04512025
15.9
44.1
61.7
70
NONE
0.0
0.0
20.8
30
2CE04510525
2
5.3
12.7
22.4
30
2CE04510725
2
7.5
18.0
29.1
30
2CE04511025
10.6
25.5
38.4
40
2CE04511525
15.9
38.2
54.3
60
2CE04512025
21.2
51.0
70.2
80
NONE
0.0
0.0
11.1
15
2CE04510746
2
6.8
8.2
13.5
15
2CE04511046
2
10.1
12.1
18.4
20
2CE04511546
2
13.6
16.4
23.7
25
2CE04512046
2
19.5
23.5
32.6
35
NONE
0.0
0.0
8.5
15
2CE04511058
10.6
10.2
14.7
15
2CE04511558
15.9
15.3
21.1
25
2CE04512058
21.2
20.4
27.5
30
NONE
0.0
0.0
39.4
60
2CE04510506
4.0
19.2
39.4
60
2CE04510706
5.6
26.9
43.2
60
2CE04511006
8.0
38.5
57.6
60
2CE04511506
11.9
57.2
81.0
90
2CE04512006
15.9
76.4
105.1
110
NONE
0.0
0.0
39.4
60
2CE04510506
5.3
22.1
39.4
60
2CE04510706
7.5
31.3
48.6
60
2CE04511006
10.6
44.2
64.7
70
2CE04511506
15.9
66.3
92.3
100
2CE04512006
21.2
88.3
119.9
125
NONE
0.0
0.0
24.1
35
2CE04510525
2
4.0
11.1
24.1
35
2CE04510725
2
5.6
15.5
25.9
35
2CE04511025
8.0
22.2
34.3
35
2CE04511525
11.9
33.0
47.8
50
2CE04512025
15.9
44.1
61.7
70
NONE
0.0
0.0
24.1
35
2CE04510525
2
5.3
12.7
24.1
35
2CE04510725
2
7.5
18.0
29.1
35
2CE04511025
10.6
25.5
38.4
40
2CE04511525
15.9
38.2
54.3
60
2CE04512025
21.2
51.0
70.2
80
NONE
0.0
0.0
12.3
15
2CE04510746
2
6.8
8.2
13.5
15
2CE04511046
2
10.1
12.1
18.4
20
2CE04511546
2
13.6
16.4
23.7
25
2CE04512046
2
19.5
23.5
32.6
35
NONE
0.0
0.0
9.5
15
2CE04511058
10.6
10.2
14.7
15
2CE04511558
15.9
15.3
21.1
25
2CE04512058
21.2
20.4
27.5
30
0.8
4
24.4
140
14.1
105
55
1.3
1.3
2.6
0.0
575-3-60
5.8
44
0.8
2
0.0
460-3-60
7.1
5.2
0.0
230-3-60
14.1
105
1.3
5.2
0.0
208-3-60
7.6
0.0
230-1-60
24.4
140
1.3
7.6
0.0
208-1-60
0.8
2.6
0.0
575-3-60
5.0
36
0.8
2
0.0
1.3
5.2
0.0
230-3-60
11.4
90
1.3
5.2
0.0
1.3
7.6
0.0
230-1-60
18.0
105
1.3
7.6
0.0
3
208-1-60
18.0
105
208-3-60
11.4
90
460-3-60
6.2
45
OD Fan
Motor
FLA
Heater
Amps
Minimum
Circuit
Ampacity
Amps
Max Fuse /
BRKR
1
Size
Amps
ID Blower
Motor
FLA
Conv
Outlet
Amps
Electric Heater
Model No.
Heater
kW
Model
Tonnage
Voltage
Compressors
RLA
Each
LRA
Each
1. HACR Type per NEC.
2. These electric heaters DO NOT include a fuse box. If a fuse box is required to meet a local code (i.e. Chicago), the fuse block accessories
2FB04700825 and 2FB04700846 are available for field installation.