York DM 060 User Manual
Page 22
036-21502-002-A-0303
22
Unitary Products Group
TABLE 16: ELECTRICAL DATA - DM036 & 048 DIRECT DRIVE WITHOUT POWR’D CONVENIENCE OUTLET
NONE
0.0
0.0
30.7
45
2CE04510506
4.0
19.2
30.7
45
2CE04510706
5.6
26.9
39.2
45
2CE04511006
8.0
38.5
53.6
60
2CE04511506
11.9
57.2
77.0
80
2CE04512006
15.9
76.4
101.1
110
NONE
0.0
0.0
30.7
45
2CE04510506
5.3
22.1
33.1
45
2CE04510706
7.5
31.3
44.6
45
2CE04511006
10.6
44.2
60.7
70
2CE04511506
15.9
66.3
88.3
90
2CE04512006
21.2
88.3
115.9
125
NONE
0.0
0.0
24.3
35
2CE04510525
2
4.0
11.1
24.3
35
2CE04510725
2
5.6
15.5
24.9
35
2CE04511025
8.0
22.2
33.3
35
2CE04511525
11.9
33.0
46.8
50
2CE04512025
15.9
44.1
60.7
70
NONE
0.0
0.0
24.3
35
2CE04510525
5.3
12.7
24.3
35
2CE04510525
2
7.5
18.0
28.1
35
2CE04510725
2
10.6
25.5
37.4
40
2CE04511525
15.9
38.2
53.3
60
2CE04512025
21.2
51.0
69.2
70
NONE
0.0
0.0
12.4
15
2CE04510746
2
6.8
8.2
13.0
15
2CE04511046
2
10.1
12.1
17.9
20
2CE04511546
2
13.6
16.4
23.2
25
2CE04512046
2
19.5
23.5
32.1
35
NONE
0.0
0.0
10.1
15
2CE04511058
10.6
10.2
14.9
15
2CE04511558
15.9
15.3
21.3
25
2CE04512058
21.2
20.4
27.7
30
NONE
0.0
0.0
38.5
60
2CE04510506
4.0
19.2
38.5
60
2CE04510706
5.6
26.9
39.9
60
2CE04511006
8.0
38.5
54.3
60
2CE04511506
11.9
57.2
77.8
80
2CE04512006
15.9
76.4
101.8
110
NONE
0.0
0.0
38.5
60
2CE04510506
5.3
22.1
38.5
60
2CE04510706
7.5
31.3
45.3
60
2CE04511006
10.6
44.2
61.5
70
2CE04511506
15.9
66.3
89.1
90
2CE04512006
21.2
88.3
116.7
125
NONE
0.0
0.0
25.7
40
2CE04510525
2
4.0
11.1
25.7
40
2CE04510725
2
5.6
15.5
25.7
40
2CE04511025
8.0
22.2
34.0
40
2CE04511525
11.9
33.0
47.5
50
2CE04512025
15.9
44.1
61.4
70
NONE
0.0
0.0
25.7
40
2CE04510525
2
5.3
12.7
25.7
40
2CE04510725
2
7.5
18.0
28.8
40
2CE04511025
10.6
25.5
38.1
40
2CE04511525
15.9
38.2
54.1
60
2CE04512025
21.2
51.0
70.0
70
NONE
0.0
0.0
13.1
20
2CE04510746
2
6.8
8.2
13.1
20
2CE04511046
2
10.1
12.1
17.9
20
2CE04511546
2
13.6
16.4
23.2
25
2CE04512046
2
19.5
23.5
32.1
35
NONE
0.0
0.0
10.8
15
2CE04511058
10.6
10.2
14.9
15
2CE04511558
15.9
15.3
21.3
25
2CE04512058
21.2
20.4
27.7
30
1.3
2.2
0.0
575-3-60
6.4
52
1.3
2.2
0.0
2.3
5.0
0.0
230-3-60
14.7
130
2.3
5.0
0.0
2.3
5.0
0.0
230-1-60
25.0
135
2.3
5.0
0.0
4
208-1-60
25.0
135
208-3-60
14.7
130
460-3-60
7.7
64
1.3
2.2
0.0
575-3-60
5.8
44
1.3
2.2
0.0
2.3
4.4
0.0
230-3-60
14.1
110
2.3
4.4
0.0
2.3
4.4
0.0
230-1-60
19.2
87
2.3
4.4
0.0
3
208-1-60
19.2
87
208-3-60
14.1
110
460-3-60
7.1
54
Max Fuse /
BRKR
1
Size
Amps
RLA
Each
LRA
Each
ID Blower
Motor
FLA
Conv
Outlet
Amps
Electric Heater
Model No.
Heater
kW
Compressors
OD Fan
Motor
FLA
Model
Tonnage
Voltage
Heater
Amps
Minimum
Circuit
Ampacity
Amps
1. HACR Type per NEC.
2. These electric heaters DO NOT include a fuse box. If a fuse box is required to meet a local code (i.e. Chicago), the fuse block accessories
2FB04700825 and 2FB04700846 are available for field installation.