beautypg.com

York DM 060 User Manual

Page 19

background image

036-21502-002-A-0303

Unitary Products Group

19

TABLE 11: SUPPLY AIR BLOWER PERFORMANCE (6 TON BELT DRIVE) - SIDE DUCT APPLICATION

RPM

WATTS

RPM

WATTS

RPM

WATTS

RPM

WATTS

RPM

WATTS

RPM

WATTS

RPM

WATTS

3200

1150

2325

1182

2425

1212

2525

-

-

-

-

-

-

-

-

3000

1100

2010

1129

2090

1157

2150

1185

2225

1215

2290

1242

2360

-

-

2800

1045

1700

1074

1780

1102

1850

1131

1940

1160

2025

1190

2075

1217

2130

2600

985

1425

1015

1475

1045

1540

1075

1630

1103

1715

1135

1760

1163

1825

2400

930

1240

958

1300

990

1350

1020

1400

1051

1430

1081

1490

1111

1600

2200

-

-

905

1070

933

1160

965

1210

997

1250

1028

1285

1060

1325

2000

-

-

-

-

-

-

919

1025

950

1100

982

1130

1014

1160

1800

-

-

-

-

-

-

-

-

909

925

939

1005

968

1030

RPM

WATTS

RPM

WATTS

RPM

WATTS

RPM

WATTS

RPM

WATTS

RPM

WATTS

RPM

WATTS

3200

-

-

-

-

-

-

-

-

-

-

-

-

-

-

3000

-

-

-

-

-

-

-

-

-

-

-

-

-

-

2800

1245

2190

-

-

-

-

-

-

-

-

-

-

-

-

2600

1193

1920

1222

1990

1250

2060

-

-

-

-

-

-

-

-

2400

1142

1675

1173

1730

1205

1800

1234

1885

-

-

-

-

-

-

2200

1090

1380

1124

1450

1155

1550

1186

1640

1217

1710

1249

1775

-

-

2000

1045

1175

1077

1200

1109

1275

1140

1360

1170

1460

1205

1545

1235

1600

1800

998

1050

1028

1060

1058

1060

1087

1075

1118

1150

1148

1250

1176

1360

0.60

0.70

0.80

AVAILABLE EXTERNAL STATIC PRESSURE-IWG

3

0.20

0.30

0.40

0.50

UNIT

SIZE

(MBH)

AIR

FLOW

CFM

072

1 2

UNIT

SIZE

(MBH)

AIR

FLOW

CFM

072

1 2

AVAILABLE EXTERNAL STATIC PRESSURE-IWG

3

0.90

1.00

1.10

1.20

1.30

1.40

1.50

1. 230/460/575 Volts
2. For 208 Volts multiply values by 0.95.
3. Includes allowances for a wet evaporator coil, 1” filters, and the heat exchangers. Refer to ACCESSORY STATIC RESISTANCE Table for
resistance values on applications other than gas / electric units with side duct airflows.

This manual is related to the following products: