Connecting the panel to the xadc dc side – Xantrex Technology Xantrex AC to DC Converter XADC User Manual
Page 20

Xantrex AC to DC Converter
20
975-0301-01-01
Connecting the Panel to the XADC DC Side
When following the procedure, see Table 2 on page 24 for wire lengths and
Table 1 on page 24 for torque values.
To connect the panel to the XADC DC side:
1. Remove the DC wiring compartment panel on the XADC (see Figure 8).
2. Loosen the positive and negative screws on the DC connection lugs (see
Figure 15).
3. Route the large positive (+) red cable and negative (-) black cable from the
panel through the DC wiring compartment hole to the XADC.
4. Make the DC ground connections to the ground lug on the right hand side or
the top of the XADC, see Figure 10.
5. Slide the negative (-) black cable into the XADC negative DC connection lug
and tighten the DC negative screw.
6. Slide the positive (+) red cable into the XADC positive DC connection lug
and tighten the DC positive screw.
Figure 15 Connecting Panel to XADC DC Side
DC positive and
negative cable
DC wiring
compartment hole
Negative DC connection
lug screw
Positive DC connection
lug screw