Connecting the AC Input
When following the procedure, see Table 1 on page 24 for torque values.
To connect the AC input:
1. Route AC wires through the AC wiring compartment hole.
2. If you plan to use the ¾ in. knockout for the AC wiring, remove the outer
knockout.
3. Connect the XADC ground (green cable) to the incoming ground. It is
recommended that you use marrettes for this as they have built in insulation.
4. Connect the XADC AC neutral (white cable) to the incoming neutral. It is
recommended that you use marrettes for this as they have built in insulation.
5. Connect the XADC AC line (black cable) to the incoming line. It is
recommended that you use marrettes for this as they have built in insulation.
6. Reattach the AC wiring compartment panel.
7. Reconnect the AC by closing or engaging the main AC disconnect breaker.
Figure 9 XADC DC Connections
POS
(+)
NEG
(-)
Negative DC connection
lug screw
Positive DC connection
lug screw
Strain relief
DC wiring knockout
Ground lug (option 2)
Ground lug
(option 1)
WARNING: Shock hazard
Ensure that the AC disconnect or breaker is open on the AC line before attempting any
installation.
Figure 10 XADC AC Connections
Grommet
AC wiring
compartment hole
AC ground (green), neutral
(white) and line (black)