Choosing a location – Xantrex Technology Xantrex AC to DC Converter XADC User Manual
Page 11
Installation Instructions
975-0301-01-01
11
•
XADC converter faceplate and mounting hardware
•
Plastic bag containing two mounting tabs and related hardware, one top
mounting flange and related hardware
Choosing a Location
The XADC and AC/DC Distribution Panel must only be installed in a location
that is:
The XADC may be mounted in 3 orientations:
•
horizontally on a flat surface
•
vertically on a wall with fan vent facing left
•
vertically on a wall with fan vent facing right
Dry
Do not allow water or other liquids to drop or splash on the XADC.
Cool
While the unit will safely operate at ambient air temperatures between 14 ºF and 86 ºF
(-10 ºC and 30 ºC) and will operate de-rated between 86 ºF and 140ºF (30 ºC and 60 ºC)
— the cooler the better within this range. At ambients in excess of 140ºF (60ºC) the
XADC may shut down.
Ventilated
Allow at least 18 inches (45.7 cm) of clearance at the front of the XADC for air flow.
Ensure that the ventilation openings are not obstructed.
Safe
Do not install the XADC or panel in the same compartment as batteries or in any
compartment capable of storing flammable liquids like gasoline.
Protected from
battery gases
Do not mount the XADC or panel where it will be exposed to gases produced by batteries.
Battery gases are corrosive, and prolonged exposure to battery gases will damage them.
Figure 6 Installation Configurations
Approved Mounting Orientation
Wall Mount (Fan Left or Right)
Approved Mounting Orientation
Desktop Mount
Non-Approved Mounting Orientation
Wall Mount (Fan Up or Down)
Non-Approved Mounting Orientation
Ceiling Mount