Appendix, Specification, 34 appendix – Watlow Electric Micro-Based Autotuning Control SERIES 980/985 User Manual
Page 34: 34 specifications, Control mode, Operator interface, Input
Appendix
Control Mode
•
Single set point, non-ramping.
l
Single input, dual outputs.
l
Control outputs: User selectable as: Heat, Heat/Heat, Heat/Cool, Cool,
Cool/Cool, Heat/Alarm, Cool/Alarm
l
Outputs independent, or related via deadband for Heat/Cool.
l
ON/OFF: 3°F or 1 .7°C switching hysteresis or 0.3°F or 0.l7°C for
0.10 Units
.
l
PID parameters:
Proportional band: 0 to 999°F/0 to 555°C(3 digit only)
0 to 999°F/0 to 555°C or 0 to 99.9°F/0 to 55.5°C (3 or 4 digit)
Reset: 0.00 to 9.99 repeats per minute.
Rate: 0.00 to 9.99 minutes.
Cycle time: 1 to 60 seconds.
l
Deadband: ±99°F, ±99 units or ±55°C
±9.9°F, ±9.9 units or ±5.5°C for 0.1 decimal units)
Operator Interface
l
Membrane front panel.
l
Three or four digit 0.3” (8mm) LED diiplays.
l
MODE, AUTO/MANUAL, UP, and DOWN keys.
l
Dual digital displays.
Input
Thermocouple, RTD, and electrical process input.
Automatic cold junction compensation for thermocouple.
RTD input 2 or 3 wire, platinum, 100 ohm @ 0°C user selectable, calibrate
to JIS curve #3916 (0.003916(0.003916ohm/ohm/°C or DIN curve #3850(0.003850ohm/ohm°C
Sensor break protection de-energizes control output to protect system or
selectable bumpless transfer to manual operation.
Grounded or ungrounded sensors.
°F/°C or process variable units are user selectable.
Operating ranges user selectable.
J t/c:
32 to 999°F or
0 to 750°C (3 Digit)
32 to 1382°F or 0 to 750°C (4 Digit)
K t/c: - 3 2 8 t o 2282°F or -200 to 1250°C
T t/c:
-328 to 662°F or -200 to 350°C
N t/c:
32 to 2282°F or
0 t o 1250°C
PT 2 (Platinel2) 32 to 2543°F or
0 t o 1395°C
1° RTD:
-328 to 1112°F or -200 to 600°C
0.1° RTD:
-99.9 to 392.0°F or -99.9 to 200.0°C
0-5VDC:
-500 to 3500 units
4-20mA:
-500 to 3500 units
34
WATLOW Series 980/985 User’s Manual Appendix