Set up menu, Set up menu prompts/description, Input ranges – Watlow Electric Micro-Based Autotuning Control SERIES 980/985 User Manual
Page 26: Output
Latching: Selects whether the
output
is latching or non-latching when Output 2
is an alarm. Latching alarms must be cleared before the alarm output will reset.
Non-latching automatically resets the alarm output when the condition clears.
The range is LAt or nLA, default is nLA. This only appears if the Ot2 = AL.
Silencing: Selects alarms silencing (alarm inhibit). Appears only when
ALt = dE. If LAt, press the Auto/Man key to reset the alarm output. If nLA, alarm
automatically resets 5 seconds after power is applied.
RTD: Selects the RTD calibration curve. JIS = 0.003916 / PC
DIN =0.003850 / °C.
Chart 1-
Setup Menu
Prompts and
Descriptions.
Use this page as a master copy for configuring your Series 980/elects the low
limit of the Operating range See the model number and specification informa-
Setup
Parameters
LOC
In
rSP
DEC
C-F
rL
rH
Otl
ot2
ALt
LAt
SIL
rtd
Value
Range
Factory Default
0-3
0
J, K
(appears as H), t, n,
J
Pt2, rtd, rt.d, 0-5,4-20
Dependent on model number.
OFF, O-5,420
OFF
0, 0.0,
or
0.00
0
Dependent on input type.
C or F
F
Will not appear if In = 0-5 or 420.
rLtorH
Input
selection
dependent.
rH to rL
Input selection dependent.
Ht or CL
Ht
Ht. CL, AL
or no
AL
Pr or dE
Pr
Dependent on Ot2 = AL.
LAt or nLA
nLA
Dependent on Ot2 = AL.
OFF or On
OFF
Appears if Ot2=AL&ALt=dE.
JIS or din
JIS
Appears if In = rtd or rt.d.
Chart 2-
Input Ranges.
Input
Type
J
Sensor Range Low
Sensor Range High
32°F/0°C 999*F/750°C (3 digit)
32°F/0°C
1 382°F/750°C (4 digit)
K
-328°F/-200°C
2282°F/1250°C
I
n
32°F/0°C
2282°F/1 250°C
Pt2
rtd
(1°)
32°F/O°C
2543°F/l395°C
-328°F/-200°C
111 2°F/600°C
rt.d (0.1’)
-99.9°F/-99.9°C
392.0°F/200.0°C
0-5 (VDC)
-5.00/-50.0/-500
I
35.00/350.0/3500
I
420
(mA)
.-5.00/-50.0/-500
35.00/350.0/3500
26
WATLOW Series 980/985 User’s Manual
Setup,
Chapter 4