LTR-Net PROGRAMMER
4-6
March 1999
Part No. 001-2009-600
Cross Reference
The cross reference screen selects the Output
Alarm that is activated by each Input Alarm.
There are up to:
•
48 alarms (0-47)
•
4 (hardware) External Input Alarms
•
18 (software) Internal Alarms (see Table 1-2).
•
26 unused
There are 4 Output Alarms. An alarm condition
on any input can cause an Output Alarm. This win-
dow configures which Input Alarm activates an Output
Alarm.
NOTE: More than one alarm condition can share the
same output alarm (see Figure 4-13).
Show Alarm Map
This window displays an Alarm Map that dis-
plays those Alarm Outputs that have been mapped in
bold type. Double-clicking on these outputs lists the
Alarm Inputs that have been assigned to that output.
Figure 4-12 ALARM MAPPING
Figure 4-13 ALARM CROSS REFERENCE