beautypg.com

5800 series transmitters table – Vista Ademco N7227V5 User Manual

Page 23

background image

Section 5 - Wireless Expansion

5-5

The wireless system can identify a true low-battery situation, thus allowing the dealer or
user of the system time to arrange a change of battery and maintain protection for that point
within the system.

Some transmitters (e.g., 5802, 5802CP, and 5804) contain long-life but nonreplaceable
batteries, and no battery installation is required. At the end of their life, the complete unit
must be replaced (and a new serial number enrolled by the control).

Button-type transmitters (such as 5801, 5802, 5802MN/MN2, 5802CP, and 5804) should be
periodically tested for battery life.

The 5802MN and 5804 Button Transmitters have replaceable batteries.

Using the Transmitter Sniffer Mode

The Transmitter Sniffer mode is a procedure that verifies that all transmitters have been
properly programmed. To verify programming, refer to the TESTING THE SYSTEM section.

5800 Series Transmitters Table

Model

Description

Input Type and Special Notes

5801

Wireless Panic
Transmitter

Enroll as “3” for RF (supervised), or “4” for UR (unsupervised).
Unit has 4 pushbuttons, each with a unique input (loop) code.
Each pushbutton must be assigned to a zone.

NOTE: Input loop (button) No. 4 must always be used.

5802
5802CP

Pendant Belt Clip
(Personal Emergency)
Transmitters

Enroll as “5” for BR (button-type transmitter).

5802MN
5802MN
2

Miniature Personal
Emergency Trans.

Enroll as “3” for RF (supervised), or “4” for UR (unsupervised).
Single pushbutton-type transmitter.

5804
5804BD

Wireless Key
Transmitter

Enroll as “5” for BR (button-type transmitter).
Has 4 pushbuttons, each with a unique input (loop) code.
Each pushbutton must be assigned to a zone.

NOTE: All buttons must be assigned the same input type.

5806

5807

5808

5807L

5807LT

5807LST

5808LST

5809

Wireless Photoelectric
Smoke Detectors

Low-profile version
of the Wireless
Photoelectric Smoke
Detectors

HeatSensor, 135º
Detector/Transmitter

Enroll as “3” for RF (supervised).
At the “INPUT S/N” prompt, fault the detector as follows:

1.

On many detectors, you must press a special test switch (not test button) to

fault the detector (see detector’s instructions).

NOTE: With some detectors, you must short two contacts to fault the
detector. Disengage the detector’s cover and swing it open. These contacts
are on the PC board near a blue jumper (see detector’s instructions).
Momentarily short these contacts with a small screwdriver.
Two keypad beeps occur when the detector is faulted the first time.

2.

Wait 6 to 8 seconds, then press and release the test switch (or momentarily

short the contacts) again. If the control has accepted the input code, 3 beeps
sound and the enrolled input (loop) number is displayed.

5816
5816MN

5816

TEMP

Door/Window
Transmitter

Low Temp Sensor

Enroll as “3” for RF (supervised).
Has two unique input (loop) zones: one for a wired closed-circuit contact loop,
and the other for a built-in reed switch (used in conjunction with a magnet).
Either or both may be used.

5817

Multi-Point Universal
Transmitter

Enroll as “3” for RF (supervised).
Has three unique input (loop) codes: one for a DIP switch-set “Primary” contact
loop, and the others for two “Auxiliary” closed-circuit contact loops.
The “Primary” loop may be set for:

Repeating or Single Transmission

Normally Open or Normally Closed circuit

Slow or Fast Response

3-Minute or no Transmission Inhibit

This manual is related to the following products: