Specifications

(Corded Models)

CORDED MODELS:

APSINT1012

APSINT1024

Weight:

11.9 Kg

11.9 Kg

INVERTER
Continuous power (@ 20° C):

1000 W

1000 W

Surge power (5 seconds):

2000 W

2000 W

Efficiency (Full Load):

89%

89%

Minimum DC Fuse Rating:

170A

90A

DC Input Current @ Nominal V DC

Full Load

95A

47A

No Load

2.6A*

1.5A*

Nominal Input Volts:

12 VDC

24 VDC

DC Input Voltage Range:

10-15 VDC

20-30 VDC

Nominal Output Volts:

230 VAC ±5%

230 VAC ±5%

Nominal Output Frequency:

50

Hz ±.3%

50

Hz ±.3%

BATTERY CHARGER
Charging Capacity DC:

30 A

15 A

Maximum Cable Length

2 ft.

7 ft.

Acceptance Volts VDC:

Selectable

Selectable

14.4 V**/14.2 V Wet**/Gel

28.8 V**/28.4 V Wet**/Gel

Float Volts VDC (w/gel):

13.3 V (13.6 V)

26.6 V (27.2 V)

Input Voltage AC:

230 V

230 V

Input Current AC:

4.3 A

8.3A

LINE VAC OPERATION
Minimum Input AC Volts:

Selectable 144**,163, 182 or 201VAC

Selectable 144**, 163, 182 or 201 VAC

Maximum Input AC Volts
(Continuous, Charger at Maximum):

Selectable 259** or 264 VAC

Selectable 259* *or 264 VAC

Maximum Input Current
(Continuous, Charger at Maximum):

8.3A

8.8A

Input Frequency:

50 Hz ±10%

50 Hz ±10%

Maximum Output AC (Continuous):

4.3 A

4.3 A

Automatic Transfer Time:

4-6 ms

4-6 ms

*Load sense can reduce this to 1/30 of the listed current. **Factory default setting.

A technician may be able to convert your UPS to receive 60 Hz ±10%power. Consult Tripp Lite for details.