2.1. PROFIBUS connector

Used to connect PROFIBUS network cables. The connector is a D-Sub connector with 9 pin

female and the connector pin allocation described below follows the PROFIBUS standard.

The PDP002Z has no termination resistor. Therefore, termination resistors need to be

connected to the station on each side of the PROFIBUS network or the master, as shown in

the figure below. (The PROFIBUS connector with termination resistor are recommended.)

2.2. Status indicator

The PDP002Z has two LEDs, ST (status) and DX (data exchange) to indicate the

statuses of PROFIBUS-DP and the PDP002Z itself.

ST (Status): Red LED

LED Meanings

Off

No diagnostics present

Flashes

Waiting for parameterisation or configuration

Lights

DP status error
* For example, a station address is not set correctly.

DX (Data exchange): Green LED.

Indicates the status of the PROFIBUS network.

It lights when the PDP002Z is on-line and data exchange is possible.

Pin number

Symbol

Signal type

1 NC

Reserved

2 NC

Reserved

3

RxD/TxD-P

Send/receive data (+)

4 CNTR-P

Control

signal

5 DGND

0V

(Insulated

from the inside)

6 VP

+5V

power

7 NC

Reserved

8

RxD/TxD-N

Send/receive data (-)

9 NC

Reserved

390 ohm

*

VP(6 pin)

220 ohm

*

RxD/TxD-P

(3 pin)

390 ohm

*

RxD/TxD-N

(8 pin)

DGND(5 pin)

* 1/4W or more is recommended.

1

5 4 3 2

9 8 7 6