Profibus local/remote operation – Toshiba PDP002Z User Manual
Page 17
E6581279⑤
- 16 -
6. PROFIBUS Local/Remote Operation
The example below shows how to configure the VF-AS1/PS1 for local / remote operation.
F terminal ............ RUN command
R terminal............ PROFIBUS/Local (Terminal in this example) switching
RR/S4 terminal.... Operation frequency command
VF-AS1/PS1
F
R
CC
PP
RR/S4
Variable resistor for adjustment
10k ohm
PROFIBUS/Local
Switch
Operation command
SINK
SW1
SOURCE
CCA
cmod
(command mode selection) = 0 (terminal board)
fmod
(frequency setting mode selection 1) = 2 (RR/S4)
f112
(input terminal selection 2 (R)) = 48 (PROFIBUS/Local control)
R-CC terminal open:
VF-AS1/PS1 is controlled as slave device of PROFIBUS.
R-CC terminal closed:
F-CC terminal short to RUN
F-CC terminal open to STOP
Output frequency is set up by the RR/S4 signal input.
- Power Inverter (15 pages)
- 1800 (6 pages)
- TOSVERT VF-S11 (68 pages)
- Uninterruptible Power System G9000 (104 pages)
- Density (Consistency) Meter LQ500 (9 pages)
- MBSB80-225-43 (1 page)
- TOSNIC-7000S (53 pages)
- 1600EP Series (3 pages)
- 1500 (32 pages)
- TOSVERT VF-FS1 Series (16 pages)
- 4200FA XT1 (1 page)
- G3 Plus Pack (4 pages)
- Tosvert VF-A5 (149 pages)
- 1600 Series (3 pages)
- G9000 (100 pages)
- TEC EO1-33030 (54 pages)
- 1000 Series (2 pages)
- 1500 Plus (31 pages)
- G8000MM (6 pages)
- VT130G1 (99 pages)
- 4200FA Series (2 pages)
- VF-PS1 (10 pages)
- GX7 Series (6 pages)
- 4200FA XT (1 page)
- RMTI-EMD-HT (2 pages)
- W7 Series (6 pages)
- HX7 (6 pages)
- RELIABILITY IN MOTION 1700 (39 pages)
- 1700 Series (2 pages)
- G3 TOSVERT-130 (62 pages)
- B-852-TS12-QP (55 pages)
- 1000 (4 pages)
- E3 (7 pages)
- Adjustable Speed Drive H3 (122 pages)
- 55611-001 (2 pages)
- Black Gold Series (2 pages)
- Dura-Bull TX (6 pages)
- Current Relay RC803A-HP1 (19 pages)
- 1800 SERIES (2 pages)
- Isolated-Redundant UPS System (2 pages)
- Tosvert VF-AS1 (312 pages)
- RELIABILITY IN MOTION 1000 (54 pages)
- REMOTE-D (2 pages)
- 15-80KVA (2 pages)