beautypg.com

Operating pressures, Warning, Live electrical components – Trane WPVJ User Manual

Page 29

background image

WSHP-SVX04A-EN

29

Operating Pressures

Water Pressure Drop
Table 4 should be used to define feet of head/pressure drop. Note: To calculate feet of head, when using gauges that read
in PSIG, multiply PSI by 2.31.

Water Volume

Table 5 is provided for use in calculating glycol requirements for the WPVJ unit.

Flow Checks
For the operating temperature drop (heating) and rise (cooling), refer to Table OP1 and OP2 for the proper water tempera-
ture change. Depending on the unit size, entering water temperature and water flow rate, the cooling temperature rise is
from 8°F-16°F. Based on the same criteria for heating, the temperature drop is from 2°F-13°F.

Pressure
Using the P/T ports and one 0-60 psi pressure gauge with the P/T port adapter, measure the pressure difference between
the water-in and water-out connections.

Start-up Checklist and Log
Use the form on page 30 to log system and unit temperatures during start-up.

WARNING

Live Electrical Components!

During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with
live electrical components. Have a qualified licensed electrician or other individual who has been properly
trained in handling live electrical components perform these tasks. Failure to follow all electrical safety pre-
cautions when exposed to live electrical components could result in death or serious injury.

Table 4: Water pressure drops (WPD) in feet of head

Unit Size

GPM

Cooling

Heating

EWT

F

Ft. Head

Pressure

EWT

F

Ft. Head

Pressure

WPVJ 018

5.0

77

7.5

55

9.0

WPVJ 024

6.1

10.2

12.1

WPVJ 030

7.2

4.9

6.0

WPVJ 036

8.6

6.7

7.9

WPVJ 042

10.1

8.8

10.0

WPVJ 048

11.5

7.8

9.0

WPVJ 060

14.9

12.4

14.1

WPVJ 072

16.5

14.8

14.1

WPHF 021

5.3

77

6.9

55

7.6

WPHF 027

6.8

11.1

12.3

WPHF 035

8.7

17.9

19.8

WPHF 040

9.9

23.1

25.6

WPHF 047

11.6

15.0

16.6

WPHF 057

14.1

22.0

24.4

Unit

Model

Unit
Size

Water Side

Volume

Cubic In.

Water Side

Volume

Cubic In.

Water Side

Volume

Gallons.

WPVJ

018-024

55

0.032

0.238

WPVJ

030-042

105

0.061

0.455

WPVJ

048-072

259

0.150

1.121

This manual is related to the following products: