Installation – Trane WPVJ User Manual
Page 15

WSHP-SVX04A-EN
15
Unit Installation; WPVJ
Duct collars are provided for the WPVJ 
equipment. The duct system and dif-
fusers should be sized inaccordance 
with ASHRAE or ACCA Manual D.
1 Install a flexible connector (field
provided) for supply/return air duct 
connections on all metal duct sys-
tems.
Note: If the unit is connected to ex-
isting ductwork, an initial check of 
the mechanical system should be 
made to insure the duct has the ca-
pacity to handle the air required for 
the unit application. If ducting is too 
small, as in the replacement of heat-
ing only systems, larger ductwork 
should be installed. All existing 
ductwork should be checked for 
leaks, and repairs should be made.
2 Insulate the field ductwork with a
minimum of 1" duct insulation. 
Note: Installing the unit to an unin-
sulated ductwork in an uncondi-
tioned space may adversely affect 
the unit’s performance, as well as in-
crease noise emissions into the 
space. 
3 Install proper condensate trapping
to the equipment. The unit drain 
connection is 3/4" (19mm). When de-
signing the condensate trap, it is im-
portant to consider the unit’s draw-
thru design requiring negative pres-
sure trapping.
In a properly trapping system, when 
condensate forms during normal 
operation, the water level in the trap 
rises until there is a constant flow 
(Figure 3). It is imperative to main-
tain water in the trap and not allow 
the trap to dry out during heating 
season. Keeping the trap primed at 
all times will enable the water to 
flow properly.
Condensate piping must be installed 
to allow the cleanable condensate 
pan to be removed for cleaning. 
Minimum clearances for drain pan 
removal are 22" (sizes 018 and 024), 
25" (sizes 030 and 042), and 27" (siz-
es 048 through 072).
4 Flush System. See page 17 for sys-
tem flushing.
Water Connection 
For vibration isolation, it is recom-
mended that flexible steel braided 
hoses be installed instead of hard pip-
ing between the supply/return risers 
and the equipment.
Trane offers 4-types of hose kit varia-
tions:
• Stainless steel braided flexible
hose with manual shut-off (ball) 
valves
• Stainless steel braided flexible
hose with manual deluxe shut-off 
(ball) valves
• Stainless steel braided flexible
hose with manual circuit-setter 
valve
• Stainless steel braided flexible
hose with automatic balancing 
valve
Additional accessories, such as a 
strainer are recommended for use to 
eliminate contaminants from entering 
the co-axial water-to-refrigerant heat 
exchangers.
Installation
Figure 3: Negative pressure trap
