Low Voltage Wiring for Field
Provided Thermostats/Zone
Sensors
Ensure that the AC control wiring be-
tween the controls and the unit’s ter-
mination point does not exceed three
(3) ohms/conductor for the length of
the run.

Note: Resistance in excess of 3-ohms
per conductor may cause component
failure due to insufficient AC voltage
supply.

Check all loads and conductors for
grounds, shorts, and mis-wiring.

Use copper conductors unless other-
wise specified.

Do not run the AC low voltage wiring
in the same conduit with the high volt-
age power wiring.

Table 3: 24V AC conductors

Distance

from unit to Control

Recommended

Wire Size

000-460 feet

18 gauge

461-732 feet

16 gauge

733-1000 feet

14 gauge

Thermostat Location
Location of the room thermostat/zone sensor cis an important element of effec-
tive room control.

Areas where the thermostat or zone sensor should not be located include : be-
hind doors, or corners; Near hot or cold air ducts; Near radiant heat (heat emitted
from appliances or the sun); Near concealed pipes or chimneys; On outside walls
or other non conditioned surfaces; In airflows from adjacent zones or other units
(Figure 7).

Installation
Low Voltage Wiring

Figure 7: Thermostat/sensor location