Installation – Trane WPVJ User Manual
Page 17

WSHP-SVX04A-EN
17
Connecting a Distributed Pump 
Kit to a Closed Loop System
All piping external to the unit is the re-
sponsibility of the installer. The water 
pipe installation must be done in ac-
cordance with local codes. If no local 
code applies, national codes should be 
followed. It is the contractor’s respon-
sibility to know and adhere to all appli-
cable codes.
Water inlet and outlet to the unit’s wa-
ter-to-refrigerant heat exchanger are 
clearly marked on the submittal draw-
ings found on pages 7 through 13. The 
supply and return piping must be in-
stalled correctly to the unit to ensure 
the safety devices will work properly. 
Units that are not piped accordingly 
will not obtain the manufacturers war-
ranty.
A pump module and hose kit (Figure 5) 
may be used to connect the unit to 
closed loop piping.
Using Antifreeze
In areas of the country where entering 
water temperatures drop below 45°F 
or where piping is being run through 
areas subject to freezing, the loop 
must be freeze protected by using an 
approved antifreeze solution to pre-
vent the earth loop water from freez-
ing inside the heat exchanger. 
Methanol, Ethylene, and Propylene 
Glycol are the most commonly used 
antifreeze solutions. Consult your geo-
thermal unit supplier for the best solu-
tions in your area.
Propylene glycol is not recommended 
in installations where the water tem-
perature are expected to fall below 
30°F. At extreme temperatures, the vis-
cosity increases to the point where 
normal loop circulating pumps cannot 
maintain proper flow.
Calculate the approximate volume of 
water in the system by using the re-
quirements detailed in Table 2. Add 
three gallons to this total to allow for 
the water contained in the hose kit and 
geothermal unit.
Table 2: Required Antifreeze by volume
Cleaning and Flushing 
the Water Loop
After the piping system is complete, 
cleaning and flushing the water loop 
should be done to avoid trash settle-
out in the condenser (Figure 6). An ex-
tra pipe may be necessary to connect 
the hose kits. 
1  Electrical power to the unit should 
be disconnected.
2 Double back the supply hose and 
connect directly to the return riser 
valve. 
3 Fill the water system with clean wa-
ter using the water make up connec-
tions. Note: Air vents should be 
opened during filling.
4  With the air vents closed, start the 
circulating pump and then crack the air 
vents to bleed off the trapped air, as-
suring circulation through all compo-
nents of the system. Note: Make up 
water must be available to the system 
to replace the volume formerly occu-
pied by the air that is bled off.
Type of
Antifreeze
Minimum Temperature for
Freeze Protection
10°F 15°F 20°F 25°F 30°F
Methanol
25% 21% 16% 10%
3%
Propylene
Glycol
23% 21% 19%
9%
6%
Ethylene Glycol 20% 19% 16% 14% 12%
5  With the air vented and the water 
circulating, the entire system should 
be checked for leaks with repairs made 
as required.
6 Check and adjust the water/air level 
in the expansion tank.
7 Operate the boiler (if used) by rais-
ing the loop temperature to approxi-
mately 85°F. Make checks per 
manufacturer’s instructions. During 
this operation, visual checks should be 
made for leaks that may have occurred 
due to increased heat. Repair as re-
quired.
8  Open the system at the lowest point 
for the initial blow down (making sure 
the make up water is equal to the wa-
ter being dumped). Continue blow 
down until the water leaving the drain 
runs clear, but not less than 2 hours.
9  Shut down pumps and boiler (if 
used). Reconnect the hoses to the 
proper supply/return for each unit, 
placing the water-to-refrigerant heat 
exchanger in the water circulating sys-
tem. Note: Vents should be open when 
the pumps and boiler are shut down.
10 Refill the system and bleed off any 
air. Add antifreeze to the system in cli-
mates where ambient temperature 
falls below freezing, using the propor-
tion of antifreeze shown in Table 2.
Installation
From Units
W.O.
To Units
W.I.
Bronze or Cast Iron Pump
Purging Cap (2)
Shut-off 3-way Valve (2)
1" MPT x barb fittings
1" MPT x barb elbows with
pressure temperature ports
and 10’ of rubber hose with
4 hose clamps
Figure 5: Pump module and hose kit
Figure 6: System flushing
