Water piping – Toshiba ESTIA A09-01P User Manual
Page 9

Quick Reference Guide - Page 9
Water Piping
• Install water pipes according to the regulations of respective countries. 
• Install water pipes in a freeze-free place. 
• Make sure that water pipes have sufficient pressure resistance (The setting value of the pressure 
relief valve is 0.3 MPa). 
• Do not use zinc plated water pipes. When steel pipes are used, insulate both ends of the pipes. 
 
Water Connections 
• Install a strainer with 30 to 40 meshes (procure locally) at 
the water inlet of the Hydro Unit. 
• Install drain cocks (procure locally) for water charge and 
discharge at the lower part of the Hydro Unit. 
 
Water Piping Limitations
s
Design the water pipe length within the QH 
characteristics of the pump (flow-rate and pump 
head). 
The maximum height difference for the water pipes i
7 metres. 
 
 
 
 
Piping to hot water tank (option
)
Water supplied to the hot water cylinder is branched by a 
motorized 3-way valve (procured locally). 
Connect the hot water cylinder to port A (open when 
energized) of the valve. 
 
Piping to 2-zone operation (option)
To perform 2-zone temperature control circulate water using another pump (procured locally) 
through a motorized mixing valve (procured locally) and a buffer tank (procured locally). 
 