Toshiba ESTIA A09-01P User Manual
Page 18

Quick Reference Guide - Page 18
3-way mixing valve connection
Required Actuator Specification 
Electrical Specification:230 V; 50 Hz; <100 mA 
The 3-way mixing valve is used to achieve the temperature differential needed in a 2-zone heating 
system. 
• Connect the 3-way mixing valve in accordance with the diagrams below:- 
 
 
Hot water cylinder connection (optional) 
• Please refer to “Electrical supply/cable specifications” for fuse/cable size and for 
connection details. 
Electrical Connection (Hot Water Cylinder Electric Heater) 
• The electric heater, incorporated in the hot water cylinder, requires a separate supply to Hydro 
Unit. 
• Connect the hot water cylinder heater electrical supply in accordance with shown below: 
Live conductor: Terminal L on Terminal Block 03 
Neutral conductor: Terminal N on Terminal Block 03 
Earth Conductor: Earth terminal on Terminal Block 03 
• Connect the hot water cylinder heater to the Hydro Unit as shown below: 
Live conductor to hot water cylinder: Terminal 1 on Terminal Block 03 
Neutral conductor to hot water cylinder: Terminal 2 on Terminal Block 03 
Earth conductor to hot water cylinder: Earth terminal on Terminal Block 03 
Electrical Connection (Hot Water Cylinder temperature Sensor) 
• Connect the hot water cylinder temperature sensor as shown below to terminals A & B on 
Terminal Block 06 in the Hydro Unit. 
• Please ensure that the interconnecting cable, between the Hydro Unit and the hot water cylinder, 
is connected to earth at both ends of the cable using the shield wire. 
 