2-way valve (for cooling) connection
Required Valve Specification: 
Electrical Specification: 230 V; 50 Hz; <100 mA 
Return Mechanism: 2-wire spring return. 
• The Hydro Unit has the facility to connect a 2-way valve to 
isolate Space Conditioning Units that do not perform cooling, 
when Cooling Mode is selected. 
• Connect the 2-way valve in accordance with the diagram 
(opposite):- 
 
3-way valve (diverter) connection
Required Valve Specification: 
Electrical Specification: 230 V; 50 Hz; <100 mA 
Valve Diameters: Port A, Port B: Ø 1 1/4" 
Return Mechanism: 3 types of 3-way valve (diverter) can be used. 
Set the 3-way valve in use with the DIP switch SW13-1 on the Hydro Unit board. 
 
Diverter Valve 
Description
SW13-1
Type 1
2-wire spring return
OFF
Type 2
3-wire SPST
OFF
Type 3
3-wire SPDT
ON
Continuous operation of the valve motor at the fully open position is not recommended. 
• The 3-way diverter valve is used to select either domestic hot water or space heating. 
• Connect the 3-way diverter valve in accordance with the diagram below:- 