Outdoor alarm indication, Alarm indications (cont) – Toshiba ESTIA A09-01P User Manual
Page 30

Quick Reference Guide - Page 30
Alarm Indications
(cont)
A09
Overheat preventive operation malfunction Auto-reset: When operation mode is changed
A11
Release preventive operation malfunction This alarm occurs when the Hydro Unit enters the forced-
stop zone 10 times. 
P31
Self-hydro unit is stopped due to alarm of other hydro unit. When alarm occurs in an hydro unit in the 
group, other hydro units must also be stopped with refrigerant control. 
When alarm E03, L03 or L07 occurs in the header unit in the group, other hydro units must also be 
stopped 
because they do not know which header unit (remote controller) to follow. 
Auto-reset: When the first alarm is reset 
Outdoor Alarm indication
Alarm
indication
Main failure part
Description
F04
Outdoor unit discharge 
temperature sensor TD 
defect 
When open- or short-circuit of discharge temperature sensor TD is 
detected 
F06
Outdoor unit temperature 
sensor TE or TS defect 
When open- or short-circuit of heat exchanger temperature sensor 
TE or TS is detected 
F08
Outdoor unit outside air 
temperature sensor TO 
defect 
When open- or short-circuit of outside air temperature sensor TO is 
detected 
H01
Compressor breakdown
When min-Hz is reached by current release control or when short-
circuit current (Idc) is detected after direct current excitation 
H02
Compressor locked
When compressor lock is detected
H03
Current detector defect
When abnormal current is detected in AC-CT or phase loss is 
detected 
H06
Low-pressure system defect Ps pressure sensor defect or low-pressure protective operation
L29
Other outdoor unit faults
Other outdoor unit faults: 1) Inter-MCU communication error between 
IPDU and CDB 2) abnormal GBT heat sink temperature 
L31
Phase sequence error, etc.
When phase sequence of 3-phase power supply is incorrect 
(thermostat OFF operation continued), etc. 
P03
Abnormal outdoor unit 
discharge temperature 
When abnormal temperature is detected by discharge temperature 
release control 
P04
High-pressure system 
defect 
When high-pressure switch , IOL is activated or when abnormality is 
detected by high-pressure release control by TE 
P22
Outdoor unit fan defect
When over current or lock in outdoor unit fan drive circuit is detected
P26
Inverter Idc operation
When short-circuit protection is activated for compressor driver 
devices (G-Tr, IGBT) 
P29
Position detection error
When compressor motor position detection error is detected
 
 