Sensor Temperature Monitoring Function

The sensor sensing temperature is displayed on the remote controller. This function allows you to make sure whether
the sensor is installed properly.

1) Press the TEST

+ CL

buttons for four seconds or more.

2) Select the Code No. with the TEMP.

buttons.

3) Press the TEST

button to exit the test mode.

Code No.

Location

Indication

06

Return water temperature °C

08

Hot water temperature °C

09

Hydro unit

2-zone sensor temperature °C

0A

Hot water cylinder temperature sensor °C

0B

Motorized mixing valve position

60

Heat exchanger temperature °C

61

Outside air temperature °C

62

Outdoor unit

Refrigerant discharge temperature °C

63

Refrigerant intake temperature °C

6A

Current value (in the inverter) A

70

Compressor operating frequency

F4

Hydro unit AC pump total operating hours x100 hours

F5

Operating hours

Hot water cylinder heater total operating hours x100 hours

F6

Hydro unit heater total operating hours x100 hours

Fault Symptoms

Symptom

Possible cause

Corrective action

Incorrect remote controller setting

Check remote controller operation and temperature
setting

Room is not heated or

Incorrect function code setting

Check function code setting with the function code
table.

Backup heater disconnected

Check backup heater and bimetal thermostat.

cooled. Water is not hot
enough.

Insufficient capacity

Check selection of equipment.

Sensor defect

Check whether temperature sensor is installed at
the normal position.

Power is not supplied.

Check power supply wiring.

Nothing is displayed on
the remote controller.

Incorrect setting

Check DIP switch setting on the Hydro Unit board.
Check the setting with the function code table.

Air bite in the pump

Release air completely according to the procedure.

Flow rate switch is

Low hydraulic pressure

Set hydraulic pressure considering pipe height, and
replenish water until manometer shows a value of
set hydraulic pressure or more.

Strainer is clogged.

Clean the strainer.

activated. Error code
[A01]

Large resistance on the hydro side

Widen water path to the hydro unit or adopt a
bypass valve.

Malfunction of motorized 3-way
valve for hot water supply

Check wiring and parts.

Excessive hydraulic pressure

Set hydraulic pressure considering pipe height, and
replenish water until manometer shows a value of
set hydraulic pressure or more.

Insufficient capacity of expansion
tank

Check expansion tank capacity compared to total
water amount. If it is insufficient, install another
expansion tank.

Hot water leaks from
pressure relief valve.

Expansion tank failure

Check the air pressure.