Notes on System Design

• The input water temperature to the Hydro Unit must be 55°C or less.
Especially, be careful when there is an external heating source such as a boiler.
When hot water over 55°C returns, it may result in a failure of the unit or water leakage.
• The flow rate of the circulating water must meet the following range:-
11 and 14 kW

17.5 L/minute or more

8 kW

13 L/minute or more

If the flow rate becomes less than the minimum, the protective device is activated to stop operation.
Ensure the flow rate with a bypass valve, etc. when you use a flow rate valve for the Hydro Unit.
• Do not drive water by power other than the pump built in the Hydro Unit.
• The backup heater operates supplementary to exert a prescribed capacity when the heat pump
cannot exert its capacity at a low outside temperature.
• Install the Hydro Unit and water pipes in a place in which they do not freeze.
• Make the water circuit closed. Never use it as an open circuit.
• To prevent damage to the system during outdoor defrost the circulating water must be 20 litres
or more

. If total water amount is not enough, the unit may not function fully due to protective

operation.

Options required for each function

Toshiba Supply

Procure locally

Purpose

Part name

Model code

Part name

Space Heating

-

-

Radiator(s),

Fan coil(s),

Under floor heating

Space Heating &

Space Cooling

(All Rooms)

-

-

Fan coil(s) only

Space Heating &

Space Cooling

(partly heating only)

- -

Fan coil(s) plus

Radiator(s)

or Under floor heating

Motorized 2-way

valve

150L Hot water cylinder

HWS-1501CSHM3-E

150L Hot water cylinder

HWS-1501CSHM3-UK

210L Hot water cylinder

HWS-2101CSHM3-E

210L Hot water cylinder

HWS-2101CSHM3-UK

300L Hot water cylinder

HWS-3001CSHM3-E

Domestic Hot Water

300L Hot water cylinder

HWS-3001CSHM3-UK

Motorized 3-way

valve

Earth leakage breaker

Motorized mixing

valve

Circulator pump

2-zone control

-

-

Buffer tank

Interlocking with

boiler

Output control board kit

(1)

TBC-PCIN3E Boiler

Interlocking with

booster heater

- -

Electric

heater