3 operation under shutdown, 4 operation of manual bypass switch, Operation (special conditions) – Tripp Lite 30kVA User Manual

Page 9: Switching ups to “bypass” mode, Switching ups to “normal” mode

background image

9

Condition

LCD Display Message

Overload Shutdown

ON BYPASS
OVERLOAD 150%
SHUTDOWN...
VERSION: XXXXXXX

UPS Output Short Circuit

ON BYPASS
SHORT CIRCUIT!
SHUTDOWN...
VERSION: XXXXXXX

Overtemperature

ON BYPASS
HIGH TEMP!
SHUTDOWN...
VERSION: XXXXXXX

DC BUS Overvoltage

ON BYPASS
DC BUS O.V.P.!
SHUTDOWN...
VERSION: XXXXXXX

DC BUS Failure

ON BYPASS
DC BUS FAIL!
SHUTDOWN...
VERSION: XXXXXXX

Condition

LCD Display Message

R/S/T Inverter Output Failure

ON BYPASS
R OUTPUT FAIL!
SHUTDOWN...
VERSION: XXXXXXX

Low Battery

BYPS OFF NO O/P
LOW BATTERY!
SHUTDOWN...
VERSION: XXXXXXX

Remote Shutdown

BYPS OFF NO O/P
REMOTE SHUTDOWN
SHUTDOWN...
VERSION: XXXXXXX

Emergency Stop

BYPS OFF NO O/P
EMERGENCY STOP!
SHUTDOWN...
VERSION: XXXXXXX

Your UPS will shut down and the LCD will display a message if it detects one of the following conditions. Note: For all conditions, the “Input,”
“Output” and “Bypass” LEDs will be illuminated.

Warning: Failure to follow this procedure could damage the unit and void its warranty.

Warning: When installing the unit, verify that any maintenance bypass panel used is configured correctly before applying power to the unit.

Turn this switch to “BYPASS” before performing any maintenance on the UPS with the connected load supported. Connected equipment will receive fil-
tered AC mains power, but will not receive battery power in the event of a blackout.

SWITCHING UPS TO “BYPASS” MODE

• Press the “OFF” button.
• Turn the “Manual Bypass” Switch clockwise from NORMAL to BYPASS.
• Turn the Main Input Switch Circuit Breaker OFF.

SWITCHING UPS TO “NORMAL” MODE

• Turn the Main Input Switch Circuit Breaker ON.
• Turn the “Manual Bypass” Switch counterclockwise from BYPASS back to NORMAL.
• Press the “ON” button.

5.3 Operation Under Shutdown

5.4 Operation Of Manual Bypass Switch

5. Operation (Special Conditions)

(continued)