Specifications – Tripp Lite 30kVA User Manual
Page 12
200810029 93-2285
12
The specifications listed below are for Tripp Lite model SU20K3/3 and SU30K3/3 which each include two modules: a power module and
a battery module. The two modules are also sold separately with their own individual model numbers.
+ Backup times are expandable with additional Battery Modules, sold separately. The policy of Tripp Lite is one of continuous improvement. Specifications are subject to change without notice. This product designed and
engineered in the USA.
Regulatory Compliance Identification Numbers
For the purpose of regulatory compliance certifications and identification, your Tripp Lite product has been assigned a unique series number. The series number can be found on the product nameplate label, along with all required
approval markings and information. When requesting compliance information for this product, always refer to the series number. The series number should not be confused with the marking name or model number of the product.
FCC Specifications for Models with FCC Approval:
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including
interference that may cause undesired operation. This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable
protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the
instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at
his own expense. The user must use shielded cables and connectors with this product. Any changes or modifications to this product not expressly approved by the party responsible for compliance could void the user's authority to
operate the equipment.
Model: SU20K3/3
Includes:
Power Module
Battery Module
Model: SU20K3/3PM
Model: BP240V33
Input
Input Voltage
120/208V AC, 3ø, 4 Wire (plus ground), wye
Input Frequency
60 Hz ± 3 Hz
Voltage Correction Range
88-144/166-250V AC
Input Current (Per Phase, On-Line)
60A
Inrush Current
<300A
Power Factor (Full Load)
>0.95
Efficiency (Full Load/On-Line)
>89%
Circuit Breaker
200A (3p)
Input Bypass Circuit Breaker
200A (3p)
Output
VA
20000
Watts (Power Factor: 0.8)
16000
Waveform (On-Line)
Sinewave
Waveform (On-Battery)
Sinewave
Output Voltage (RMS)
120/208V AC, 3ø, 4 Wire (plus ground), wye
Output Frequency
60 Hz (± 0.1 Hz on battery)
Voltage Regulation
±2%
Max. Harmonic Distortion
(Non-Linear Full Load)
<5%
Overload Capabilities
102% (continuous), 102%~125% (1 min.),
125%~150% (30 sec.), 150% (2 sec.)
Short Circuit Capability
167A
Crest Factor
3:1
Battery
Battery Type
Sealed, Lead-Acid, 12V/33 AH
Battery Quantity
20
Protection
2x 125A/400V fuse
Typical Backup Time (Half Load)
30+ min.
Typical Backup Time (Full Load)
12+ min.
Operation
On-Line Transfer Time
(Line to Battery, Battery to Line)
0 ms
Audible Noise (Full Load @ 1 meter)
<65 dBA
Indicators
Includes an LCD Display and LEDs (AC Line In, Bypass Line In, AC to DC, DC to AC,
AC Output, Battery Back-Up, Bypass).
Communications
Includes an RS-232 DB9 female connector, an AS-400 DB9 female
connector, a dry contact DB9 female connector and an accessory slot.
Connections
Input Terminal Block
100A
Output Terminal Block
100A
External Battery Terminal Block
100A
Physical Specifications
Power Module Dimensions (H x W x D) 34 x 15 x 26 in (87 x 38 x 66 cm )
Power Module Shipping Weight:
(330 lb) 149 kg
Battery Module Dimensions (H x W x D) (20 x 18 x 36 in) 51 x 45 x 91 cm
Battery Module Shipping Weight:
(611 lb) 278 kg
Model: SU30K3/3
Includes:
Power Module
Battery Module
Model: SU30K3/3PM
Model: BP240V33
Input
Input Voltage
120/208V AC, 3ø, 4 Wire (plus ground), wye
Input Frequency
60 Hz ± 3 Hz
Voltage Correction Range
88-144/166-250V AC
Input Current (Per Phase, On-Line)
90A
Inrush Current
<300A
Power Factor (Full Load)
>0.95
Efficiency (Full Load/On-Line)
>89%
Circuit Breaker
200A (3p)
Input Bypass Circuit Breaker
200A (3p)
Output
VA
30000
Watts (Power Factor: 0.8)
24000
Waveform (On-Line)
Sinewave
Waveform (On-Battery)
Sinewave
Output Voltage (RMS)
120/208V AC, 3ø, 4 Wire (plus ground), wye
Output Frequency
60 Hz (± 0.1 Hz on battery)
Voltage Regulation
±2%
Max. Harmonic Distortion
(Non-Linear Full Load)
<5%
Overload Capabilities
102% (continuous), 102%~125% (1 min.),
125%~150% (30 sec.), 150% (2 sec.)
Short Circuit Capability
250A
Crest Factor
3:1
Battery
Battery Type
Sealed, Lead-Acid, 12V/33 AH
Battery Quantity
20
Protection
2x 125A/400V fuse
Typical Backup Time (Half Load)
18+ min.
Typical Backup Time (Full Load)
6+ min.
Operation
On-Line Transfer Time
(Line to Battery, Battery to Line)
0 ms
Audible Noise (Full Load @ 1 meter)
<65 dBA
Indicators
Includes an LCD Display and LEDs (AC Line In, Bypass Line In, AC to DC, DC to AC,
AC Output, Battery Back-Up, Bypass).
Communications
Includes an RS-232 DB9 female connector, an AS-400 DB9 female
connector, a dry contact DB9 female connector and an accessory slot.
Connections
Input Terminal Block
100A
Output Terminal Block
100A
External Battery Terminal Block
100A
Physical Specifications
Power Module Dimensions (H x W x D) 34 x 15 x 26 in (87 x 38 x 66 cm )
Power Module Shipping Weight:
(330 lb) 149 kg
Battery Module Dimensions (H x W x D) (20 x 18 x 36 in) 51 x 45 x 91 cm
Battery Module Shipping Weight:
(611 lb) 278 kg
9. Specifications