2. Expanded Functions
F
E
D
C
B 8
7 0
B
Abn Busy Status
0
TermSTS
B+1
Transmission error information (if TermSTS is H0B)
Inside the parameter:
Transfer parameter
S20LP
Ethernet
MID (network type)
2
3
CH (channel of self-station)
1 or 2 (max. two S20LP’s on T3H)
1 to 4 (max. four EN311’s on T3H)
Target station No.
1 to 64
0 (fixed)
Request command
0 (fixed)
H0021: Register read/write
(for other commands, refer to EN311
manual)
Transfer size
(number of words)
1 to 128
(max. 84 words for T or C register)
(designation across T511 and T512 is
not allowed)
1 to 485
(max. 323 words for T or C register)
(designation across T511 and T512 is
not allowed)
Register type
H0000: XW/YW register
H0001: W register
H0002: LW register
H0003: RW register
H0004: D register
H0005: F register (CPU)
H
∗∗
05: Expanded F register
(IC card, 8k words/bank,
∗∗
is bank No. 01 - 0F)
H
∗∗
06: Expanded F register
(IC card, 64k words/bank,
∗∗
is bank No. 01 - 02)
H0007: T register
H0008: C register
H0009: SW register
Leading address
Designates the leading register address to be transferred
Response time limit
Specifies the time limit of the response from target-station. (0.1 s units)
When the bit F is set to ON, the following default value is used.
S20LP ...... 4.1 s
Ethernet ... 30 s
Target-station IP address
N/A
Designates the IP address of the
target-station
Target-station UDP port No.
N/A
Designates the UDP port No. of the
target-station