54

PROSEC T3H

2. Expanded Functions


B+17

B+16

Initial status STS

B+17 B+16

F

0 F C 8 4 0

Initial operation mode

00 : Manual mode

01 : Auto mode

10 : Cascade mode

11 : (Reserve)


Direct / reverse selection

0 : Direct

1 : Reverse


B+19

B+18

MV upper limit MH (-25 to 125 %)

Data range: -25.0 to 125.0

B+21

B+20

MV lower limit ML (-25 to 125 %)

Data range: -25.0 to 125.0

B+23

B+22

MV differential limit DMV (0 to 100 %/

t)

Data range: 0.0 to 100.0

B+25

B+24

Control interval setting n (1 to 32767 times)

Data range: 1.0 to 32767.0

Executes PID every n scan. Therefore, control interval

t = n

×

constant scan interval

(It is treated as n = 1 when n

0)



C+1

C

Manipulation value MV (-25 to 125 %)

Data range: -25.0 to 125.0

C+3

C+2

:

Internal work area

C+15

C+14


Operation


1. When the instruction input is OFF:

Initializes the FPID3 instruction.

Operation mode is set as specified by B+17

B+16.

A+10 bit 0, 1

B+16 bit 0, 1

Auto mode SV is set as specified by B+9

B+8. ASV

ISV

Manual mode MV is set as current MV.

MMV

MV

Internal calculation data is initialized.

MV remains unchanged.

2. When the instruction input is ON:

Executes PID calculation every n scan which is specified by B+25

B+24. The following operation modes

are available according to the setting of A+11

A+10.

Auto mode
This is a normal PID control mode with ASV as set value.
Set value differential limit DSV, manipulation value upper/lower limit MH/ML and differential limit DMV
are effective.
Bump-less changing from auto mode to manual mode is available. (Manual mode manipulation value
MMV is over-written by current MV automatically. MMV

MV)