T3h overview – Toshiba PROSEC T3H User Manual

Page 21

background image

User’s Manual

19

1. T3H Overview


(7) Data transmission module

The following types of data transmission modules are available.

Type Description

Remarks

EN311

Ethernet

10BASE5 or 10BASE2, 10 Mbps,
computer link, T3H to T3H, and socket
service

Only for T3H

SN321 TOSLINE-S20

High-speed

Co-axial

T3/T3H

SN322

control

data

Optical

common

SN323

link, 2 Mbps

Co-axial/optical

SN325

TOSLINE-S20LP

High-speed control data link, 2 Mbps,
4 k words scan memory, optical loop

Only for T3H

MS311

TOSLINE-F10

Field network,

Master station

T3/T3H

RS311

750 k bps

Remote station

common







(8) Module internal current consumption

The table below shows the internal 5 Vdc current consumption (max. value) of each
T3H module. Use this data to check the power capacity.

Type

Internal 5 Vdc

consumption

Type

Internal 5 Vdc

consumption

CPU

PU325H

1.5 A

AC output

AC363

530 mA

PU326H

1.5

A

AC364

800

mA

Expansion I/F

IF321

40 mA

Relay output

RO364

170 mA

IF311

20

mA

RO363S

100

mA

IF351

20 mA

Analog input

AD368

450 mA

IF312

800 mA

Analog output

DA364

180 mA

IF352

700

mA

DA374

180

mA

IF353

700 mA

Pulse input

PI312

800 mA

DC input

DI334

100 mA

ASCII

AS311

1.0 A

DI334H

100 mA

Change detect

CD332

300 mA

DI335

170 mA

Ethernet

EN311

700 mA

DI335H

170 mA

TOSLINE-S20

SN321

800 mA

AC input

IN354

120 mA

SN322

800 mA

IN364

120

mA

SN323

800

mA

DC output

DO333

320 mA

TOSLINE-S20LP SN325

800 mA

DO334

210 mA

TOSLINE-F10

MS311

600 mA

DO335

400

mA

RS311

600

mA

NOTE

(1) Maximum number of modules available on one T3H is as follows.

Ethernet: 4

TOSLINE-S20 and S20LP total: 2

TOSLINE-F10: 8


(2) Ethernet module and TOSLINE-S20LP are under development.