beautypg.com

T3h overview – Toshiba PROSEC T3H User Manual

Page 17

background image

User’s Manual

15

1. T3H Overview


(2) Expansion interface module

The expansion interface modules for the T3, i.e. IF311, IF351, IF312, IF352 and
IF353, are also used with the T3H. When the IF311 or IF312 is used with the T3H, up
to three expansion units can be connected, as same as the T3.
On the other hand, the IF321 is a dedicated expansion interface module for the T3H.
When the IF321 is used instead of the IF311, up to 6 expansion units can be
connected. In the maximum configuration, the T3H can control up to 76 I/O modules.

Type Description

Remarks

IF321

For basic unit
(2 channels)

Standard expansion type.
2 m max. between units, 6 m

Only for T3H

IF311

For basic unit
(1 channel)

max. in total cable length for each
channel.

T3/T3H
common

IF351

For expansion unit

IF312

For basic unit

Long-distance expansion type.

IF352

For middle expansion
unit

40 m max. in cable length.
(one channel only)

IF353

For end expansion
unit


IF321

CH1

CH2

Channel 2 expansion
(connected to the expansion #4)

Channel 1 expansion
(connected to the expansion #1)