Temco Tool 41DVN User Manual
Page 42

42
41DVN / DVSN Direct Vent Gas Fireplace
20009999
T203
Air shutter
12/12/03 djt
IMPORTANT: Always check for gas leaks with a
soap and water solution. Do not use open flame for
leak testing.
NOTE: These are minimum settings. Air shutter open-
ings may be increased to prevent flame sooting.
Conversion Kits
Change Natural Change Propane
Model
to Propane
to Natural
41DVN
41DVCKP
--
41DVP
--
41DVDSN
20007906
--
41DVDSP
--
Normal and High
Direct Vent Units - Inputs - Orifice Size - Altitude
BTU/Hr
BTU/Hr
Manifold Pressure Orifice 0 - 2000ft. Altitude in USA
Model
Min. Input
Max. Input
@ Max.
Orifice 0-4500ft Altitude in Canada
41DVN
20,000
30,000
3.5”w.c.
#37 DMS
41DVP
19,000
27,000
10.0” w.c.
#53
41DVDSN
--
30,000
3.5” w.c.
#37 DMS
41DVDSP
--
27,000
10.0” w.c.
#53
Air Shutter Settings
Opening
Model
“A”
41DVN
1/4”
41DVP
Fully Open
41DVDSN
1/4”
41DVDSP
Fully Open
“A”