Selection guide

0

Splitter boxes FTM
(not governed by the type of fieldbus)

Digital inputs/outputs

Analog inputs/outputs

Degree of protection

IP 67

Bus connection

Internal bus + 24 V power supply by M12, 6-pin connectors

Splitter box type

Compact

Expandable

Compact

Connector type

M8

M12

M8

M12

M12

Modularity
Number of channels

8 I
8 I/O

8 I
8 I/O
16 I
16 I/O

8 I
8 I/O

8 I
8 I/O
16 I
16 I/O

4 I

4 O

Digital inputs

Voltage

c 24 V

Conformity to IEC 11331-2

Type 2

Digital outputs

Voltage

c 24 V

Type

Transistor

Current/output

0.5 A

Maximum supply by internal
bus

4 A

Analog inputs/outputs

Nature

Current

Voltage

Current

Voltage

Measuring range

0 to 20
mA
4 to 20
mA

c ± 10 V,

c 0 to
10 V

0 to 20
mA
4 to 20
mA

c ± 10 V,

c 0 to
10 V

Resolution

16 bits

15 bits +
sign

12 bits

11 bits +
sign

Conversion time

≤ 2 ms/channel

Diagnostics

Per channel

I/O short-circuit
Wire breakage fault
Faulty sensors/actuators

I/O short-circuit
Wire breakage fault
Faulty sensors/actuators

Splitter box type

FTM
1D
p08
C08

FTM
1D
ppp
C12

FTM
1D
p08
C08E

FTM
1D
ppp
C12E

FTM
1AE04
C12C

FTM
1AE04
C12T

FTM
1AS04
C12C

FTM
1AS04
C12T