General Specifications
Item
CJ2H-
CPU64-EIP
CPU65-EIP
CPU66-EIP
CPU67-EIP
CPU68-EIP
Enclosure
Mounted in a panel
Grounding
Less than 100
Ω
CPU Rack Dimensions
90 mm × 65 mm × 80 mm (W × H × D)
Weight
280 g or less
Current Consumption
5 VDC, 0.82 A
Use
Environment
Ambient Operating Temperature
0 to 55°C
Ambient Operating Humidity
10% to 90%
Atmosphere
Must be free from corrosive gases.
Ambient Storage Temperature
−20 to 70°C (excluding battery)
Altitude
2,000 m or less
Pollution Degree
2 or less: Conforms to JIS B3502 and IEC 61131-2.
Noise Immunity
2 kV on power supply line (Conforms to IEC 61000-4-4.)
Overvoltage Category
Category II: Conforms to JIS B3502 and IEC 61131-2.
EMC Immunity Level
Zone B
Vibration Resistance
Conforms to JIS C60068-2-6.
5 to 8.4 Hz with 3.5-mm amplitude, 8.4 to 150 Hz
Acceleration of 9.8 m/s
2
for 100 min in X, Y, and Z directions (10 sweeps of 10 min each = 100 min total)
Shock Resistance
Conforms to JIS C60068-2-27.
147 m/s
2
, 3 times in X, Y, and Z directions (100 m/s
2
for Relay Output Units)
Battery
Life
5 years at 25°C
Model
CJ1W-BAT01
Applicable Standards
Conforms to cULus and EC Directives.