Installation, Rigid pipe venting systems, Inst alla tion – Regency LIBERTY L900-NG User Manual

Page 16

background image

Regency

®

L900 Direct Vent Gas Fireplace

16

INST

ALLA

TION

RIGID PIPE VENTING SYSTEMS

BASIC HORIZONTAL & VERTICAL TERMINATIONS

Rigid Pipe Vent Systems offer a complete
line of component parts for installation of both
horizontal and vertical installations. Many items
are offered in decorative black, as well as gal-
vanized fi nish.

The minimum components required for a basic
horizontal termination are:

1 AstroCap

XL

1 90

o

Elbow

1 Rigid

Pipe

Adaptor

1 Wall

Thimble

1 Length of pipe to suit wall thickness

The minimum components required for a basic
vertical termination are:

1 Vertical

Termination

Cap

1 Rigid

Pipe

Adaptor

1 Lengths of pipe to adequately
penetrate

roof

1 Ceiling

Firestop

1 Flashing
1 Storm

Collar

Wall thickness is measured from the back
standoffs to the inside mounting surface of
termination cap. For siding other than vinyl
furring strips may be used, instead of the vinyl
siding standoff, to create a level surface to
mount the vent terminal. The Terminal must
not be recessed into siding. Measure the wall
thickness including furring strips.

If a Vinyl Siding Standoff is required (it must
be used with vinyl siding), measure to outside
surface of wall without siding and add 2
inches.

Alternate

Horizontal Termination

Caps

Rigid Pipe

Adapter

(770-994)

Pipe Length

Vertical Terminal

Storm Collar

Flashing

Ceiling Firestop

24”

Pipe

Length

Adj.Pipe Length

11" - 14-5/8"

90 Elbow

o

AstroCap XL

Termination Cap

(Part #946-623/P)

Wall Thimble

(Mandatory in all

Horizontal Terminations)

Vinyl Siding

Standoff (Optional)

Vent Guard - if required*

(Part #946-506/P)

When using Rigid Vent other than

Simpson Dura-Vent, 3 screws must be

used to secure rigid pipe to adaptor.

The FPI AstroCap XL

TM

is certifi ed for installations using FPI venting systems as well as Simpson Dura-Vent

®

Direct Vent GS and Selkirk Direct-Temp.

AstroCap XL

TM

is a proprietary trademark of FPI Fireplace Products International Ltd. Dura-Vent® and Direct Vent GS are registered and/or proprietary

trademarks of Simpson Dura-Vent Co. Inc.

This product has been evaluated by Intertek for
using a Rigid Pipe Adaptor in conjunction with
Duravent Direct-Vent GS and Selkirk Direct-
Temp systems. Use of these systems with
the Rigid Pipe adaptor is deemed acceptable
and does not affect the Intertek WHI listing of
components.

WARNING:

Do not combine venting components from
different venting systems.

Use of the the AstroCap XL

TM

is acceptable

with all systems.

INSTALLATION

Part # 5DT-ST14 (14")
Part # 5DT-ST36 (36")

IMPORTANT NOTE

• The Simpson Dura-Vent and Selkirk Direct
Temp horizontal termination caps cannot
be used in any applications.
• Only the AstroCap XL and Snorkels are
certifi ed for horizontal terminations.

* A Vent Guard is required when the AstroCap
is installed above grade at 7 feet or lower.