L676E Direct Vent Gas Fireplace

20

INST

ALLA

TION

Horizontal Venting with Two (2) 90

o

Elbows

Horizontal Venting with Three (3) 90

o

Elbows

One 90

o

elbow = Two 45

o

elbows.

Option V

H + H1

A)

2' Min. 4' Max.

B)

3' Min. 5' Max.

C)

4' Min. 6' Max.

D)

5' Min. 7' Max.

E)

6' Min. 8' Max.

With these options, maximum total
pipe length is 30 feet with minimum
of 6 feet total vertical and maximum
8 feet total horizontal.

Please note minimum 1 foot
between 90

o

elbows is required.

One 90

o

elbow = Two 45

o

elbows.

Option V

H V + V1 H + H1

A)

2' Min. 1' Max. 3' Min. 2' Max.

B)

2' Min. 2' Max. 5' Min. 4' Max.

C)

3' Min. 2' Max. 7' Min. 5' Max.

D)

4' Min. 3 Max. 9' Min. 6' Max.

E)

5' Min. 4' Max. 10' Min. 7' Max.

F)

6' Min. 6' Max. 11' Min. 9' Max.

With these options, max.
total pipe length is 30 feet
with min. of 11 feet total
vertical and max. 9 feet total
horizontal.

Please note min. 1 foot
between 90

o

elbows is

required.

VENT RESTRICTOR SETTING:
Vent restrictor must be at Set 0 for both NG and LP.

VENT RESTRICTOR SETTING:
Vent restrictor must be at Set 0 for both NG and LP.

INSTALLATION