Installation, High elevation, Gas connection – Regency E21-LP1 User Manual

Page 8

background image

8

Regency E21 Gas Fireplace Insert

HIGH ELEVATION

This unit is approved in Canada for altitude

0 to 4500 ft. (CAN/CGA 2.17-M91) with the

orifi ce supplied.

System Data

For altitude: Natural Gas 0-2000 ft.

Propane:

0-4500 ft.

Burner Inlet Orifi ce Sizes:

Natural Gas Propane

Burner

#43 #54

Max. Input Rating
- Natural Gas

23,500 Btu/h

- Propane

22,500 Btu/h

Min. Input Rating

- Natural Gas

--

+/-5% 11,750 Btu/h

-Propane +/-5% 11,250 Btu/h

Supply Pressure
Natural Gas

min. 5.0" w.c.

Propane

min. 12.0" w.c.

Manifold Pressure (High)
Natural Gas

3.8" +/- 0.2" w.c.

Propane

11" +/- 0.2" w.c.

Circulation Fan: 120 VAC, 60 Hz
Variable Speed: 127 CFM, thermally
activated

NATURAL GAS E21-NG1

For altitude: 2000 ft - 4500 ft.

Burner Inlet Orifi ce Size:

44 DMS

Max. Input Rating

22,000 Btu/h

Min. Input Rating

+/-5% 11,000 Btu/h

INSTALLATION

GAS CONNECTION

Only persons licensed to work with gas piping

may make the necessary gas connections to

this appliance.

The gas connection is a 3/8" NPT accessible on

the left side of the unit. The gas line connection

may be made of rigid pipe, copper pipe or an

approved fl ex connector. (If you are using rigid

pipe, ensure that the valve can be removed

for servicing.) Since some municipalities have

additional local codes it is always best to consult

with your local authorities and the CAN/CGA

B149 installation code.

For USA installations follow local codes and/or

the current National Fuel Gas Code, ANSI

Z223.1.

When using copper or fl ex connectors use only

approved fi ttings. Always provide a union so that

gas lines can be easily disconnected for burner

or fan servicing. Flare nuts for copper lines and

fl ex connectors are usually considered to meet

this requirement.

Important: Always check for gas leaks

with a soap and water solution or gas

leak detector. Do not use open fl ame

for leak testing.

For minimum and maximum supply pressure

see the System Data table.

1) If the appliance is to be installed into an

existing chimney system, thoroughly clean

the masonry fi replace that has been chosen

for the Regency Gas Fireplace.

2) The appliance is provided with an opening on

the left hand side of the control compartment

for the gas line.

Note: During any pressure testing of the gas

supply piping system that exceeds test pressures

of 1/2 psig, this appliance and its individual

shut-off valve must be disconnected from the

piping system. If test pressures equal to or less

than 1/2 psig are used then this appliance must

be isolated from the piping system by closing

its individual manual shut-off valve during the

testing.

CAUTION: If the glass is removed for

servicing, it must be replaced prior to

operating the appliance. The glass must

be fixed in the closed position when

operating.