beautypg.com

Installation, Mechanical installation, Electrical installation – Raypak LONMARK Y-200 User Manual

Page 6: Check your power source

background image

6

INSTALLATION

If the controller was not mounted on the boiler by the

factory, care should be taken to select a suitable

mounting location. The controller should be mounted

on a solid and permanent base. The unit should be

readily accessible for maintenance and installation

purposes, and should be mounted so that the display

is at a height and location convenient for viewing.

Mechanical Installation

Install the controller within 30 feet of the boiler(s). It

must be mounted vertically with the conduit holes fac-

ing downward. The conduit holes are sized to

accommodate standard 1/2" conduit fittings. If addi-

tional or larger conduit fittings are required, locate the

conduit connections on the bottom of the module.

Slave units, if present, should be installed adjacent to

the master unit. (Y-304 slave cable is approximately

five feet long.)

Mount the controller using the mounting bracket and

appropriate hardware in four (4) places.

A minimum of eighteen (18) inches clearance from the

front, and six (6) inches clearance on all other sides is

required for service access. The hinged right side of

the box should be installed with sufficient clearance

(minimum 3” from bolt hole on the right side) to open

the cover.

An electrical distribution sub-panel containing appro-

priate disconnect switches and surge suppressors is

required at or near the equipment location(s).

Electrical Installation

Requires: 120 VAC, Draws 0.5 amp; 60 Hz.

120 VAC Feeder Circuits: Install a surge protection

device sized appropriately for your installation at each

module.

Install a separate disconnect means for each load.

Use appropriately sized wire for equipment as defined

by NEC and/or local code. All primary wiring should be

no less than 125% of minimum rating.

It is strongly recommended that the controller and the

boiler(s) be supplied from the same power source.

Install conduit as appropriate.

Check Your Power Source

Using a Volt-ohm meter, check the following voltages

at the terminal block inside the unit:

AC = 108 Volts AC Minimum, 132 Volts MAX

AB = 108 Volts AC Minimum, 132 Volts MAX

BC = Must be less than .6 Volts AC

NOTE: Shielded 18 (AWG) gauge stranded wire

must be used to connect the sensors to the

controller. The shielded cable should be protected by

conduit whenever possible.

CIRCUIT

BREAKER

WHITE

GROUND

BLACK

GREEN

A B C

VOLT-OHM

METER

Fig. 1: Volt-ohm Meter

NOTE: Minimum 18 AWG, 105°C, stranded wire

must be used for all low voltage (less than 30 volts)

external connections to the unit. Solid conductors

should not be used because they can cause

excessive tension on contact points. Install conduit

as appropriate. All high voltage wires must be the

same size (105°C, stranded wire) as the ones on the

unit or larger.